Descargar Imprimir esta página

Panasonic CU-5E34NBE Manual Del Usuario página 60

Ocultar thumbs Ver también para CU-5E34NBE:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 65
5-5. Wiring Instructions for the Outdoor Unit
CAUTION
Be sure to correctly align inter-unit cables A, B, C, D and E.
Indoor unit E
E is the indoor unit with
Terminal board
refrigerant tubing that is
1 2 3
connected to service valve
E (top) of the outdoor unit.
Indoor unit D
D is the indoor unit with refrigerant
Terminal board
tubing that is connected to
1 2 3
service valve D (fourth from
the bottom) of the outdoor unit.
Indoor unit C
C is the indoor unit with refrigerant
Terminal board
tubing that is connected to
1 2 3
service valve C (third from the
bottom) of the outdoor unit.
Indoor unit B
B is the indoor unit with refrigerant
Terminal board
tubing that is connected to
1 2 3
service valve B (second from
the bottom) of the outdoor unit.
Indoor unit A
A is the indoor unit with
Terminal board
refrigerant tubing that is
1 2 3
connected to service valve
A (bottom) of the outdoor unit.
Use a dedicated air conditioner circuit for power.
To make connections to the outdoor unit, remove the inspection panel and tubing panel.
Do not bring the inter-unit cables or power cable into contact with tubing or service valves.
Use outdoor unit cable fasteners and fasten the inter-unit cables at the location where the cables are double-
sheathed.
Arrange the wiring so that the inter-unit cables are contained in the inspection panel and tubing panel, as shown
in Fig. 31.
1
E
1
C
Inter-unit cables
1.0 mm
2
(not provided)
Label E
E
Inter-unit cables
1.0 mm
2
(not provided)
Label D
D
Inter-unit cables
1.0 mm
2
(not provided)
Label C
C
Inter-unit cables
1.0 mm
2
(not provided)
Label B
B
Inter-unit cables
1.0 mm
2
(not provided)
Label A
A
Outdoor unit
Terminal board
2
3
1
2
3
L
N
D
2
3
1
2
3
1
2
3
B
A
Be sure to perform grounding.
Attach a ground wire to either the
outdoor unit or indoor unit.
If there is a grounding terminal
inside the room, use the grounding
screw inside the indoor unit.
Be sure to apply the provided labels to both
ends of the inter-unit cables to prevent mis-
wiring. The units will not function if the wiring
connections are incorrect.
Fig. 31
18
Power:
Single-phase,
220 - 230 - 240 VAC 50Hz
Leakage breaker/fuse link
(not provided)
Ground
Power cable (not provided)
(3.5 mm
2
: Less than 26 m)

Publicidad

loading

Este manual también es adecuado para:

Cu-5e34nbe-c1 852 362 21