1-5. INSTALLATION DIAGRAM
Open as a rule
More than 19-11/16 in.
(500 mm) if the front and
both sides are open
More than
3-15/16 in.
(00 mm)
Open as a rule
More than 19-11/16 in. (500 mm)
if the back, both sides and top
are open
Outdoor unit installation
6-6/7
Air inlet
Air inlet
2 - (15/32 × 6/7)
oval holes (Base bolt M10)
En-3
More than 3-15/16 in. (100 mm)
More than 7-7/8 in. (200 mm) if there
are obstacles to both sides
More than 13-25/32 in.
(350 mm)
2-U-shape notched holes
37-2/5
(Base bolt M0)
23-5/8
Air outlet
Unit : inch
After the leak test, apply insulat-
ing material tightly so that there is
no gap.
When the piping is to be at-
tached to a wall containing metals
(tin plated) or metal netting, use
a chemically treated wooden
piece 25/32 in. (20 mm) or thicker
between the wall and the piping
or wrap 7 to 8 turns of insulation
vinyl tape around the piping.
To use existing piping, perform
COOL operation for 30 minutes
and pump down before removing
the old air conditioner. Remake
flare according to the dimension
for new refrigerant.
Units should be installed by licensed contractor according to
local code requirements.
74
Air inlet
2 - 2 × 22
oval holes (Base bolt M10)
PARTS TO BE PROVIDED AT YOUR SITE
(A) Power supply cord*
(B) Indoor/outdoor unit connecting wire*
(C) Extension pipe
(D) Wall hole cover
(E) Piping tape
Extension drain hose (or soft PVC
(F)
hose, 19/32 in. (15 mm) inner diam-
eter or hard PVC pipe VP16)
(G) Refrigeration oil
(H) Putty
(I) Pipe fixing band
(J) Fixing screw for (I)
(K) Wall hole sleeve
Soft PVC hose, 19/32 in. (15 mm)
(L)
inner diameter or hard PVC pipe
VP16 for drain socket (1)
* Note:
Place indoor/outdoor unit connecting wire (B) and
power supply cord (A) at least 3 ft. (1 m) away from
the TV antenna wire.
The "Q'ty" for (B) to (K) in the above table is quan-
tity to be used per indoor unit.
Outdoor unit installation
950
2-U-shape notched holes
(Base bolt M0)
600
Air inlet
Air outlet
Little
amount
2 to 7
2 to 7
Unit : mm