Descargar Imprimir esta página

Ferroli BLUEHELIX PRO RRT 24 C Instrucciones De Uso, Instalación Y Mantenimiento página 182

Publicidad

Idiomas disponibles

Idiomas disponibles

Procedure for modifying parameter SC12:
Put the boiler in heating or DHW mode and press the reset button (ref. 6 fig. 1) for 10 seconds.
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) to set and view 120.
Then press the "DHW +" button (ref. 2 fig. 1) to set 123.
Press the reset button (ref. 6 fig. 1) once.
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
The display shows Sc flashing; press the reset button once.
The display shows Sc alternating with 01 flashing;
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
Press the "DHW +" button and the display shows "00";
Press the "DHW +" button until the display shows "02";
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display shows "Sc" alternating with "15".
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes
put the boiler in TEST mode and check the CO
Procedure for modifying parameters SC12 and SC13:
Put the boiler in heating or DHW mode and press the Reset button (ref. 6 fig. 1) for 10 seconds.
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) to set and view 120.
Then press the "DHW +" button (ref. 2 fig. 1) to set 123.
Press the Reset button (ref. 6 fig. 1) once.
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
The display shows Sc flashing; press the reset button once.
The display shows Sc alternating with 01 flashing;
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
Press the "DHW +" button and the display shows "00";
Press the "DHW +" button until the display shows "03";
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display shows "CA" and "LI" alternately to indicate that a fur-
ther calibration is being performed.
after just over a minute the calibration mode will end and the display will show "C" alternating with "15" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC13" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display "SC" appears alternately to "15".
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes
put the boiler in TEST mode and check the CO
182
BLUEHELIX PRO RRT 24 C
value at maximum and minimum power with an analysis instrument.
2
value at maximum and minimum power with an analysis instrument.
2
cod. 3541Q530 - Rev. 00 - 10/2018
optimization.
2
optimisation.
2
optimization.
2
EN

Publicidad

loading