Procedure for modifying parameter SC12:
•
Put the boiler in heating or DHW mode and press the reset button (ref. 6 fig. 1) for 10 seconds.
•
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) to set and view 120.
•
Then press the "DHW +" button (ref. 2 fig. 1) to set 123.
•
Press the reset button (ref. 6 fig. 1) once.
•
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
•
The display shows Sc flashing; press the reset button once.
•
The display shows Sc alternating with 01 flashing;
•
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
•
Press the "DHW +" button and the display shows "00";
•
Press the "DHW +" button until the display shows "02";
•
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
•
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
•
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
•
press the "heating +" button to confirm the value. The display shows "Sc" alternating with "15".
•
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes
•
put the boiler in TEST mode and check the CO
Procedure for modifying parameters SC12 and SC13:
•
Put the boiler in heating or DHW mode and press the Reset button (ref. 6 fig. 1) for 10 seconds.
•
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) to set and view 120.
•
Then press the "DHW +" button (ref. 2 fig. 1) to set 123.
•
Press the Reset button (ref. 6 fig. 1) once.
•
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
•
The display shows Sc flashing; press the reset button once.
•
The display shows Sc alternating with 01 flashing;
•
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
•
Press the "DHW +" button and the display shows "00";
•
Press the "DHW +" button until the display shows "03";
•
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
•
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
•
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
•
press the "heating +" button to confirm the value. The display shows "CA" and "LI" alternately to indicate that a fur-
ther calibration is being performed.
•
after just over a minute the calibration mode will end and the display will show "C" alternating with "15" with the con-
tinuous flame symbol.
•
press the "DHW +" or "DHW -" button to set the "SC13" parameter value to the value that allows CO
•
press the "heating +" button to confirm the value. The display "SC" appears alternately to "15".
•
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes
•
put the boiler in TEST mode and check the CO
182
BLUEHELIX PRO RRT 24 C
value at maximum and minimum power with an analysis instrument.
2
value at maximum and minimum power with an analysis instrument.
2
cod. 3541Q530 - Rev. 00 - 10/2018
optimization.
2
optimisation.
2
optimization.
2
EN