Descargar Imprimir esta página

D+H LDx-1400-5 Manual Original página 6

Publicidad

Technical Data
Type
Power supply
Nominal force
Input power
Stroke length
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*
Opening and Closing Ranges LDx-1400 (LDx-1800)*
1400 N (1800 N)
1400 N (1800 N)
1400 N (1800 N)
* Programmable with software SCS (only ACB) ** Running direction programmable with SCS (only ACB)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges C3 and C2, the drive
runs "OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
6/20
LDx 1x00-5 /-ACB
LDx-1400-5
42 W / 65 VA
Closing edge protection = activated (3 repetitions of stroke)
3 mm
O1*
2 mm/s
85 mm
O2*
2 mm/s
2 mm
1 mm/s
O3*
LDx-1400-5-ACB
230 V AC, +10 % / -15 %, 50 Hz
1400 N
max. 90 mm ± 2 % *
approx. 5000 N (Depending on the fastening)
>20.000 double strokes
30 %, With cycle time 10 minutes
Aluminium, silver anodised EV1
IP 40 (IP 44 with inserted gaskets)
-5 ... +75 °C
B300 (30 min / 300 °C)
≤ 90 %, not condensing
LpA ≤ 45 dB(A)
Locking relief = activated
CLOSED**
OPEN**
In addition, the drive is equipped with passive
protection. The closing speed in closing range C2
and C1 is reduced to 1 mm/s.
Significantly greater forces can be
exerted at the secondary closing edges.
Danger of crushing hands and fingers!
English
LDx-1800-5
LDx-1800-5-ACB
1800 N
52 W / 75 VA
5 mm
800 N (1000 N)
C1*
1 mm/s
20 mm
C2*
400 N (500 N)
1 mm/s
65 mm
C3*
800 N (1000 N)
2 mm/s
99.828.02 1.3/01/20

Publicidad

loading

Este manual también es adecuado para:

Ldx-1800-5Ldx-1400-5-acbLdx-1800-5-acb