Descargar Imprimir esta página

LEGRAND IME CONTO D4-Pt CE4TBDTCL1 Manual De Instalación página 29

Publicidad

• Technical characteristics
Case
Dimension (w x h x d)
Connections
Degree of protection
Weight:
Display
Type:
Auxiliary supply
Derived from the voltage terminals (Self-supplied)
Measurement
Three-phase 3 and 4-wire network
Voltage (TRMS)
Inirect measurement
Three-phase rated voltage Un:
Power consumption voltage circuit:
Current (TRMS)
Indirect measurement
Current circuit power consumption
Short-time overcurrent
(IEC/EN 62053-21, IEC/EN 62053-23):
Frequency
Rated frequency
Permitted variation
Energies
Cod. CE4TB0PCL1 - CE4TBDTCL1 - CE4TBMTCL1
Cod. CE4TB0PMID - CE4TBDTMID - CE4TBMTMID
3x100/173...3x230/400V
U
3x100...3x400V
I
CE4TB0PCL1
CE4TBDTCL1
CE4TBMTCL1
cl.
CE4TB0PMID
I
CE4TBDTMID
71,2 x 92,4 x 66mm
CE4TBMTMID
cl.
0,1 Wh/imp
LED
COM
L1-
L2-L3
V1-V2-V3
1 C
RS485
Mbus
(-25°C) - (55°C )
Front face IP54, Terminals IP20
210g
Graphic, backlit 1.8 inches (256x128)
3x100...3x400V - 3x100/173...3x230/400V
Max. 1,5VA three-phase
Cod.
CE4TB0PCL1 - CE4TBDTCL1 - CE4TBMTCL1
Cod.
CE4TB0PMID - CE4TBDTMID - CE4TBMTMID
Max. 1,8W per phase
20 Imax / 0,5sec.
F
50Hz; 60Hz
n
49...51 Hz, 59...61Hz
Active energy accuracy class: 1 (IEC/EN 62053-21)
Reactive energy accuracy class: 2 (IEC/EN 62053-23)
Active energy accuracy class: B (EN 50470-1, -3
Reactive energy accuracy class: 2 (IEC/EN 62053-23)
CONTO D4-Pt
Three-phase energy meter
CAT III
CT/1A - /5A
I
= 0,01A I
= 5A I
= 6A
min
n
max
cl. 1 Wh (EN 62053-21)
cl.2 varh (EN 62053-23)
CT/5A
I
= 0,05A I
= 5A I
= 6A
min
n
max
cl.B Wh (EN 50470-1,3)
cl.2 varh (EN 62053-23)
Mbus
RS485 Modbus
MAX
Recommended
11 mm
2
torque 1,6 to 2Nm
1 x 10 mm
COMBI PZ2
1 x 10 mm
2
2
1 x 16 mm
MAX
Recommended
8 mm
torque 0,2Nm
1 x 1 mm
2
0,5 x 2,5mm
1 x 1 mm
2
1 x 1,5 mm
2
CT/1A - / 5A
I
: 0,01A - I
: 5A - I
min
n
max.
CT/ 5A
I
: 0,05A - I
: 5A - I
min
n
max.
6A
6A
29

Publicidad

loading