MENUS
9.
MCE/C provides 2 menus: user menu and advanced menu.
The user menu is accessible from the Home Page by briefly pressing the central button "Menu".
The advanced menu is accessible from the Home Page by pressing the central button "Menu" for 5 seconds.
Table 2 describes the parameters sensitive to the inverter and provided in the advanced menu. To exit the
advanced menu, scroll through all parameters using the central button.
Parameter
symbol
Electric pump rated frequency Set the
Fn
value stated on the electric pump
Electric pump rated current
In
Set the value stated on the electric pump
Direction of rotation. Modify this
Rt
parameter to invert the direction of
Minimum rotation frequency of the electric
Fm
Maximum rotation frequency of the
FM
Numero di giri al minuto massimo
SM
--
Differential pressure type of sensor
H0
Maximum electric pump head.
Fc
Inverter carrier frequency
Dry running power. If you want to enable
protection against dry running, set the
DR
value of the absorbed power at Fn
(normal frequency) in dry running
conditions, increased by 20%.
Time that passes between switching off
ET
one pump and switching on the other in
Table 2: Advanced menu – Sensitive inverter parameters
Description
dataplate.
dataplate.
rotation.
pump.
electric pump
dell'elettropompa.
twin systems.
ENGLISH
Range
50 - 200
MCE-110
1,0 – 24,0
0 – (8/10)*Fn
(8/10)*Fn - Fn
12*Fn - 60*Fn
Ratiometric with fs = 4 bar
Ratiometric with fs = 10 bar
2.0 –fs pressure sensor
2,5 - 10
0.0 – 15.0
8
Measurement
MCE-150
1,0 – 32,0
0 – 1
--
unit
Hz
A
--
Hz
Hz
r.p.m.
--
m
kHz
W
s

Publicidad

loading

Este manual también es adecuado para:

Mce-110/c