Page 6.0
Page 6.0 is displayed if "economy" mode has been chosen on page 5.0 and allows
setting of the percentage reduction value of the set-point.
This reduction will be carried out if digital input I2 is energised.
If a twin system is used (see Par. 5.6 ) on page 7.0 you can set one of the 3
Page 7.0
possible twin operating modes:
If the twin communication cable is disconnected the systems automatically figure as
Single, working completely independent of each other.
Page 8.0
On page 8.0 it is possible to choose the parameter to be displayed on the Home
Page:
Page 9.0
On page 9.0 you can choose the language in which to display the messages.
Page 10.0
On page 10.0 you can display the alarms log by pressing the right button.
If the system finds any faults it records them permanently in the alarms log (up to a
Alarms Log
maximum of 15 alarms). For each recorded alarm a page composed of 3 parts is
displayed: an alphanumeric code that identifies the type of fault, a symbol that
illustrates the fault in graphic mode, and a message in the language selected on
Page 9.0, giving a brief description of the fault.
By pressing the right button you can scroll through all the pages of the log.
2 questions appear at the end of the log:
ENGLISH
Alternate every 24h: The 2 inverters alternate in regulation every 24
operating hours. If one of the 2 malfunctions, the other takes over
regulation.
Simultaneous: The 2 inverters work at the same time and at the same
speed. This mode is useful when a flow rate is required that cannot be
provided by a single pump.
Main/Reserve: Regulation is always performed by the same inverter
(Main), the other (Reserve) takes over only if there is a malfunction of
the Main one.
Measured head expressed in metres
Estimated flow rate express in m
Rotation speed expressed in revs per minute (rpm)
Voltage measured on the analogue input 0-10V
Power distributed expressed in kW
Operating hours
Liquid temperature measured on the input "Press1" (if available)
Liquid temperature measured on the input "Press2" (if available)
1. "Reset Alarms?"
Pressing OK (left button) resets any alarms still present in the system.
2. "Delete Alarms Log?"
Pressing OK (left button) deletes the alarms memorised in the log.
50
3
/h