Schedule to EU-Type Examination Certificate No. TÜV 99 ATEX 1496 X
VISY-Stick ... TLS; VISY-Stick (Flex) Temp TLS; VISY-Stick ... Advanced TLS and
VISY-Stick ... Flex TLS:
For EPL Ga or EPL Ga/Gb or EPL Gb, the permissible temperature range can be taken from
the following tables, depending on the variant and the temperature class:
Temperature class
T4
T3
T2
T1
For EPL Db applications, the permissible ambient temperature range depending on the
permissible surface temperature can be taken from the following table:
Dust layer ≤ 5 mm
T
5
X°C = 135 °C
X°C = T
a
The equipment is suitable for dusts with an ignition temperature of more than 270 °C under a
dust layer of 5 mm (glow temperature).
TORRIX Exd XT...; TORRIX Exd ...-A; TORRIX Exd ... Flex and TORRIX Exd ... PL:
For EPL EPL Ga/Gb or EPL Gb, the permissible temperature range can be taken from the
following tables, depending on the variant and the temperature class:
Temperature class
T6
T5
T4
T3
T2
T1
For EPL Db applications, the permissible ambient temperature range depending on the
permissible surface temperature can be taken from the following table:
Dust layer ≤ 5 mm
T
5
X°C = T
The equipment is suitable for dusts with an ignition temperature of more than 190 °C under a
dust layer of 5 mm (glow temperature).
(16) Drawings and documents are listed in the ATEX Assessment Report No. 22 203 302211
P17-F-011
Ambient temperature range
Maximum surface temperature
X°C
+ 110 °C
Ambient temperature range
Maximum surface temperature
X°C
+ 30 °C
a
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Rev. 02/11.21
-40 °C ... +75 °C
-40 °C ... +85 °C
-40 °C ... +85 °C
-40 °C ... +85 °C
With total immersion
T X°C
X°C = 135 °C
Observe EN 60079-14
-55 °C ... +50 °C
-55 °C ... +65 °C
-55 °C ... +85 °C
-55 °C ... +85 °C
-55 °C ... +85 °C
-55 °C ... +85 °C
With total immersion
T X°C
Observe EN 60079-14
Issue 03
Medium temperature range
-40 °C ... +125 °C
-40 °C ... +190 °C
-40 °C ... +285 °C
-40 °C ... +435 °C
Ambient temperature range
T
a
-40 °C ... +77 °C
-40 °C ... +85 °C
Medium temperature range
-55 °C ... +75 °C
-55 °C ... +90 °C
-55 °C ... +125 °C
-55 °C ... +190 °C
-55 °C ... +285 °C
-55 °C ... +435 °C
Ambient temperature range
T
a
-55 °C ... +85 °C
Page 7/8