GB
2.6
Technical data
2.6.1
Refrigeration data
Designation
Cooling capacity A35 / A35 * / **
Cooling capacity A50 / A35 * / **
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior
temperature (factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, exterior circuit
Air volume flow, interior circuit
Condensate separation
2.6.1 Electrical data
Designation
Rated
operating
voltage * / ****
Rated frequency *
Functional range
Power consumption *
Rated current*
Starting current*
2.6.2 Dimensions
Description
Height DTS
Height DTI
Width
Depth with cover (standard)
Installation depth DTI
Weight
Installation attitude
Unit construction
2.6.3 Other unit data
Designation
Anti-corrosion protection
Protection type
*
Data on the type plate.
***
Max. rated current UL at 60 Hz.
Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014c © Pfannenberg GmbH
Model DTI/DTS 6201C
Q
1000 W
0
Q
590 W
0
Model DTI/DTS 6201C
50 Hz
P
el
480 W
A35/A35
I
1,8 A
nom max
I
9,1 A
Start max
Model DTI/DTS 6201C
DTI: 46 kg / DTS: 47 kg
Model DTI/DTS 6201C
Standard: Galvanized, electrostatic powder-coated (200°C)
Variant: Stainless steel cover
When used as intended:
IP 54 against the switch cabinet (EN 60529).
IP 34 against the environment (EN 60529).
**
Use of optional filter mats reduces the cooling capacity.
**** With a change to the rated operating voltage, adapt the
upstream fuse; see
Model DTI/DTS 6301C
R 134a
500 g
+35°C (+95°F)
+52°C (+125,6°F)
+15°C (+59°F) bis +55°C (+131°F)
+25°C (+77°F) bis +45°C (+113°F)
885 m³/h
885 m³/h
Condensate evaporator
Model DTI/DTS 6301C
400 V 2~
50 / 60 Hz
DIN IEC 60038
60 Hz
50 Hz
570 W
770 W
2,1 A
3,5 A
Model DTI/DTS 6301C
968 mm
962 mm
410 mm
253 mm
60 mm
DTI: 50 kg / DTS: 51 kg
Vertical
Standard: Steel sheet
Model DTI/DTS 6301C
Adapting the upstream fuse .
1500 W
850 W
60 Hz
820 W
3,3 A
16 A
Page 13 / 43