Operation
4.1
General functions
NOTE
Danger of damage to the cooling unit
Operation without the unit cover prevents the adequate supply of air to the condenser and limits the intended
heating function.
Only operate the cooling unit with the unit cover installed.
The Multi-Controller (MC) has a control panel with a green LED light (1). If an error occurs, the green LED light (1)
blinks and various system information is displayed in the LCD (5); see
If assembly and installation are completed, switch on the power supply to the cooling unit.
• The cooling unit starts its operation and the LED light (1) illuminates green continuously.
• After the supply voltage has been connected and the door is closed, the units run continuously.
Exception: Energy-saving mode and cooling units with anti-freeze option.
The external temperature sensor controls the energy-saving mode; see
• The Multimaster function can connect up to six cooling units in the bus function.
• The LCD (5) displays the current operating statuses; see
• The cooling unit (2) is equipped with an electronic control unit. An internal temperature sensor (4) detects the
temperature of the air sucked in from the interior of the switch cabinet (3). If the upper or lower limit temperature
is exceeded or undercut, a fault indication is triggered.
• The green LED light (1) blinks and the LCD (5) displays the error number with temperature (°C/°F).
The ambient conditions and switch cabinet interior temperatures must correspond to the prescribed technical
data; see
Technical data.
The ambient temperature must be less than 55°C; see
Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014c © Pfannenberg GmbH
3
4
Figure 18 – Electronic control function
system information .
1
2
5
TS2 temperature
System
information.
Air flow functional principle.
sensor.
Page 26 / 43