vessels on or near the unit.
This unit intended for installation in a controlled environment (temperature controlled, indoor area free of
conductive contaminants). Avoid installing the UPS in locations where there is standing or running water, or
excessive humidity.
Do not plug the UPS input into its own output.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens,
or vacuum cleaners to UPS.
To reduce the risk of overheating the UPS, do not cover the UPS' cooling vents and avoid exposing the unit to
direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray detergent.
Do not dispose of batteries in a fire as they may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be
observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same number and type of sealed lead-acid battery. The maximum
ambient temperature rating is 40 ℃.
This pluggable type A equipment with battery already installed by the supplier is operator installable and may be
operated by laymen.
During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and
the connected loads does not exceed 3.5 mA.
Attention, hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage
still may be accessible through supply from battery. The battery supply should be therefore disconnected in the
plus and minus pole of the battery when maintenance or service work inside the UPS is necessary.
The mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible.
11. Trouble shooting
Use the following table to solve minor issues.
SYMPTOM
No LED display on the front panel.
Alarm buzzer beeps continuously
when AC supply is normal.
When power failure, back-up time is
shorten.
Mains normal but LED is flashing.
For more detailed information, contact Zigor:
30987500
QUICK GUIDE
POSSIBLE CAUSE
Battery weak.
Battery defect.
Power switch is not pressed.
Overload of the UPS.
Overload of the UPS.
Battery voltage is too low.
Battery defect due to high
temperature operation environment,
or improper operation to battery.
Power cord is loose.
sac@zigor.com
www.zigor.com
REMEDY
Charge battery up to 8 hours.
Replace with the same type of
battery.
Press the power switch again.
Verify that the load matches the UPS
capability specified in the specs.
Remove some non-critical load.
Charge battery 8 hours or more.
Replace with the same type of
battery.
Reconnect the power cord properly.
9