Variations In Operating Range - Chauvin Arnoux F 01 Manual De Instrucciones

Pinza multimetrica
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Electric shocks (test as per IEC 1000-4-5)
- 6 kV in RCD mode on the voltmeter function, aptitude
criterion B
- 2 kV on the current measurement cable, aptitude criterion B
Electromagnetic compatibility
(as per EN 61326-1 ed. 97 + A1)
Emission: class B
Immunity:
- Electrostatic discharge:
4 kV on contact, aptitude criterion B
8 kV in the air, aptitude criterion B
- Radiation fields: 10 V per m, aptitude criterion A
- Rapid transients: 1 kV, aptitude criterion B
- Directed disturbance: 3 V, aptitude criterion A
Mechanical resistance
- Free fall 1 m (test as per IEC 68-2-32)
- Impact: 0.5 J (test as per IEC 68-2-27)
- Vibration: 0.75 mm (test as per IEC 68-2-6)
Auto-extinction (as per UL94)
- Casing: V0
- Jaws: V0
- Display window: V2

4.6 Variations in operating range

Relevant
Meas. range
parameter
Battery voltage 7.5 to 10 V
Temperature
0..0.50°C
Relative
10...90% RH
humidity
Frequency
40 Hz...1 kHz
1 kHz...5 kHz
40 Hz...400 Hz
400 Hz...5 kHz
Position of the Any
conductor
position on
in the
internal
jaws
perimeter of the
(f ≤ 400 Hz)
jaws
Adjacent
Conductor
conductor
in contact with
with AC (50 Hz) the external
current running
perimeter of the
through
jaws
Conductor
0...400 V DC
clamped
or RMS
Application
0...600 V DC
of voltage
or RMS
to the clamp
Parameter
parameter
affected
All
Typical
-
V
0.05% L/10°C
A
0.1% L/10°C
W
0.1% L/10°C
≤ 1 count
V
A
0.2% L
≤ 1 count
W
V
see curve
A
see curve
A
1% L
A
40 dB
V
< 1 count
A
< 1 count
22
Effect
Max
0.2% L +1 count
0.2% L/10°C + 2 ct
0.2% L/10°C + 2 ct
0.2% L/10°C + 2 ct
0.1% L +1 count
0.3% L +2 count
0.3% L +2 count
1% L +1 count
6% L +1 count
1% L +1 count
5% L +1 count
1.5% L +1 count
35 dB
1 count
1 count

Publicidad

Tabla de contenido
loading

Tabla de contenido