Honeywell
1 Functions and features
Use in hazardous areas according to the classification
II 1G (group II, category 1G, apparatus for gas atmosphere).
The requirements of the standards
IEC60079-0, IEC60079-11, IEC60079-26 and EN1127-1 are met.
EC type test certificate
IEC type test certificate
ATEX marking
N95000 and NF503A
II 1G Ex ia IIC T6 Ga Ta: -25...55°C
II 1G Ex ia IIC T5 Ga Ta: -25...60°C
II 1G Ex ia IIC T4 Ga Ta: -25...70°C
IEC Ex marking
N95000 and NF503A
Ex ia IIC T6 Ga Ta: -25...55°C
Ex ia IIC T5 Ga Ta: -25...60°C
Ex ia IIC T4 Ga Ta: -25...70°C
2 Installation / Set-up
The units must only be installed, connected and set up by qualified staff. The
qualified staff must have knowledge of protection classes, regulations and
provisions for apparatus in hazardous areas.
Check whether the classification (see "Marking" above and marking on the
unit) is suitable for the application.
Connection only to intrinsically safe circuits which are approved with type
test certificate and do not exceed the following maximum values:
6
PTB 01 ATEX 2192
IECEx.PTB.08.0058
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
73024995a