9. Test run
Refer to the following tables for details on the check codes. (Wireless remote controller)
[ Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
Off
lamp blinking
Approx. 2.5 sec.
pattern
Self-check starts
(Start signal
received)
[ Output pattern B]
Beep
Beeper sounds
OPERATION
INDICATOR
Off
lamp blinking
pattern
Approx. 2.5 sec.
Self-check starts
(Start signal
received)
[ Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
No sound
[ Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR
lamp flashes (Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
*1 If the beeper does not sound again after the initial t o beeps to confirm the self-check start signal
not come on, there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial t o beeps to confirm the self-check start signal
received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
Beep
Beep
Beep
Beep
th
1
st
2
nd
3
rd
n
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table (i.e., n= 5 for "P5")
Beep
Beep
1
st
2
nd
On
On
On
0.5 sec.
0.5 sec.
Approx.3 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table (i.e., n = 5 for "U2")
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (Liquid or 2-phase pipe) sensor error
E6, E7
Indoor/outdoor unit communication error
P4
Drain sensor error
P5
Drain pump error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
– –
No corresponding
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U2
U1, Ud
Abnormal high pressure (63H worked)/Overheating safeguard operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal
U9, UH
synchronous signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Beep
Beep
1
st
2
nd
· · · Repeated
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table
Beep
Beep
n
th
3
rd
Off
On
On
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
Symptom
Symptom
as received and the OPERATION INDICATOR lamp does
Beep
Beep
1
st
2
nd
· · · Repeated
On
On
On
0.5 sec.
0.5 sec.
Approx.3 sec.
Number of blinks/beeps in pattern indicates the
check code in the following table
Remark
Remark
For details, check the LED
display of the outdoor controller
board.
as
23