7. Troubleshooting
Having trouble?
Noise is louder than specifications.
The indoor unit which is not operating becomes warm and a sound,
similar to water flowing, is heard from the unit.
Nothing appears in the wireless remote controller display, the display
is faint, or signals are not received by the indoor unit unless the remote
controller is close.
The operation lamp near the receiver for the wireless remote controller
on the indoor unit is flashing.
Warm air blows from the indoor unit intermittently when heat mode is off
or during fan mode.
The wireless remote controller does not operate (the indoor unit beeps
4 times).
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a
refrigerant leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and
comes into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
8. Specifications
Model
Power source (Voltage/Frequency)
Capacity (Cooling/Heating)
Dimension (Height)
Dimension (Width)
Dimension (Depth)
Net weight
Fan Airflow volume (Low-Middle-High)
Noise level (Low-Middle-High)
Notes
* Operation temperature of indoor unit.
Cooling mode: 15°C WB - 24°C WB, 59°F WB - 75°F WB
Heating mode: 15°C DB - 27°C DB, 59°F DB - 81°F DB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27°C DB (81°F DB)/19°C WB (66°F WB), Outdoor 35°C DB (95°F DB)
Heating: Indoor 20°C DB (68°F DB), Outdoor 7°C DB (45°F DB)/6°C WB (43°F WB)
*2 This figure ( ) indicates panel's.
18
TPLFYP005FM140
TPLFYP008FM140
<V/Hz>
<kW>
1.7/1.9
<inch>
<inch>
<inch>
<lbs>
28.9 (5.3)
<CFM>
230-265-280
<dB>
26-28-30
Here is the solution. (Unit is operating normally.)
The indoor operation sound level is affected by the acoustics of the
particular room as shown in the following table and will be higher than
the noise specification, which was measured in an echo-free room.
High sound-
absorbing rooms
Location
Broadcasting
examples
studio, music
room, etc.
Noise levels
3 to 7 dB
A small amount of refrigerant continues to flow into the indoor unit
even though it is not operating.
The batteries are low.
Replace the batteries and press the Reset button.
If nothing appears even after the batteries are replaced, make sure
that the batteries are installed in the correct directions (+, –).
The self diagnosis function has operated to protect the air conditioner.
Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be
sure to provide the dealer with the model name.
When another indoor unit is operating in heat mode, the control
valve opens and closes occasionally to maintain stability in the air
conditioning system. This operation will stop after a while.
* If this will cause an undesirable rise in the room temperature in
small rooms, etc., stop the operation of the indoor unit temporarily.
Switch the auto mode setting to the AUTO (single set point) mode or
AUTO (dual set point) mode. For details, refer to the included Notice
(A5 sheet) or the Installation Manual.
TPLFYP012FM140
Single, 208/230V, 60 Hz
2.8/3.2
3.6/4.0
9-21/32 (13/32)
22-7/16 (24-19/32)
22-7/16 (24-19/32)
230-280-315
245-280-335
26-30-33
26-30-34
Normal rooms
Low sound-
absorbing rooms
Reception room,
Office, hotel
hotel lobby, etc.
room
6 to 10 dB
9 to 13 dB
TPLFYP015FM140
TPLFYP018FM140
4.5/5.0
5.6/6.3
31.3 (5.3)
265-315-390
315-390-460
28-33-39
33-39-43