8. Technical specifications
MultiPlus
PowerControl / PowerAssist
AC input
Maximum feed through current (A)
Minimum AC supply current capacity for
PowerAssist (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C / 77°F (VA)
Cont. output power at 25°C / 77°F (W)
Cont. output power at 40°C / 104°F (W)
Cont. output power at 65°C / 150°F (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
CHARGER
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary output
Multi purpose relay
(5)
Protection
(2)
VE.Bus communication port
General purpose comm. port
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connections
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz; 120V 60Hz on request
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relay which can be set for general
DC undervoltage or genset start signal function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
Input voltage range: 187-265 VAC
Output voltage: 230 VAC ± 2%
(3)
Input voltage range: 187-265 VAC
(4)
Max. 50A Switches off when no external AC source available
For parallel and three phase operation, remote monitoring and system integration
Operating temp.: -40 to +65°C (-40 - 150°F (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
24/5000/120-100 230V
Yes
Input frequency: 45 – 65 Hz
100
6,3
19 – 33
Frequency
5000
4000
3700
3000
10000
94
30
Input frequency: 45 – 55 Hz
Power factor: 1
28,8
27,6
26,4
120
4
Yes
Yes, 3x
a - g
Yes, 2x
Humidity (non condensing) : max 95%
Protection category: IP 21
M8 bolts (2 plus and 2 minus connections)
M6 bolts
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
EN 55014-1, EN 55014-2, EN 61000-3-3
48/5000/70-100 230V
38 – 66
50 Hz ± 0,1%
:
5000
4000
3700
3000
10000
95
35
57,6
55,2
52,8
70
25