Engineers (ASHRAE) and the local code authorities.
(e) When cutting or drilling into wall or ceiling, do not damage electrical wiring
and other hidden utilities.
(f) Ducted fans must always be vented to the outdoors.
(g) If this unit is to be installed over a tub or a shower, it must be marked as
appropriate for the application and connected to a GFCI (Ground Fault Circuit
Interrupter) - protected branch circuit.
(h) Never place a switch where it can be reached from a tub or shower.
(i) CAUTION: For General Ventilating Use Only. Do Not Use To Exhaust
Hazardous Or Explosive Materials And Vapors.
(j) CAUTION: MOUNT WITH THE LOWEST MOVING PARTS AT LEAST 2.4 M
(8 FEET) ABOVE THE FLOOR OR GRADE LEVEL.
(k) All units are suitable for use with solid-state speed control.
The TD - MIXVENT series can be mounted in any orientation, horizontal or vertical,
and is suitable for numerous types of applications. See Figure (1). Illustration of some
typical applications.
If the installation is made to rigid or flexible ducting, then we would recommend the
correct diameter ducting is used to couple to the fan flanges. If it is necessary to
bend the duct at the discharge of the fan, then the bend radius should be as large as
possible. When rigid duct is used, make sure to use round elbows.
Before installing the product check the following points: (1) the fan impeller turns freely
and (2) there are no obstructions to the airflow.
All models include a robust mounting bracket which enables easy and quick installation
of the fan. See Figure (2) Installation
Diagrams For TD - MIXVENT Duct Fans.
Ductwork connection should be made with duct tape or duct fast-clamps (available
through your local distributor) to ensure a good seal and secure connection.
To ensure quiet operation of ENERGY STAR qualified inline and remote fans,
each fan shall be installed using sound attenuation techniques appropriate for the
installation. For bathroom and general ventilation applications, at least 8 feet of
insulated flexible duct shall be installed between the exhaust or supply grille(s) and
the fan. For remote ventilation applications, where metal duct is generally required
by code, a metal sound attenuator shall be installed between the hood and the fan.
Duct
Tape
Fan
5
Tape
Duct