The amount of refrigerant that is shown in the table below is the maximum total amount in the system.
Unit model
Maixmum total amount in the system [kg (oz)]
P072
P096
P120
P144
P168
P192
P216
P240
P264
P288
P312
P336
Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of refrigerant.
Record the added refrigerant amount on the label attached to the control box panel for future servicing.
9-9-1. Calculation of the amount of additional refrigerant
・The amount of refrigerant to be added depends on the size and the total length of the high-pressure piping and liquid piping.
・Calculate the amount of refrigerant to be charged according to the formula below.
・Round up the calculation result to the nearest 0.1 kg (0.1 oz).
(1) Units "m" and "kg" (In an R2 system)
<Formula>
・When the piping length from the outdoor unit to the farthest indoor unit is 30.5 m (100 ft) or shorter
Amount of
High-pressure pipe ø28.58
additional charge
=
total length
(kg)
× 0.36 (kg/m)
Liquid pipe ø15.88 total
+
length
× 0.2 (kg/m)
Main or sub BC controller
+
Total capacity of
Single
+
Combination
WT09115X03
33.5 (1182)
41.5 (1464)
47.5 (1676)
49.3 (1739)
50.3 (1775)
74 (2611)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
High-pressure pipe ø22.2
+
total length
× 0.23 (kg/m)
Liquid pipe ø12.7 total
+
length
× 0.12 (kg/m)
Amount (kg/unit)
J-type
1.5
JA-type
3.0
KA-type
4.7
KB-type
0.4
Amount (kg)
outdoor units
(to be added for outdoor unit)
72
0
96
0
120
0
144
0
168
0
192
4.4
216
4.4
240
4.4
192
0
216
0
240
0
264
0
288
0
312
0
336
0
384
8.8
432
8.8
Unit model
Maixmum total amount in the system [kg (oz)]
E072
E096
E120
E144
E168
E192
E192
E216
E216
E240
E240
E264
E288
E312
E336
E384
E432
High-pressure pipe ø19.05
+
total length
+
× 0.16 (kg/m)
Liquid pipe ø9.52 total
+
length
+
× 0.06 (kg/m)
Total capacity of connected
indoor units
27 or below
28 to 54
55 to 126
127 to 144
145 to 180
+
181 to 234
235 to 273
274 to 307
308 to 342
343 to 411
412 to 450
451 or above
Total capacity of
outdoor units
72
96
120
144
Single
168
192
216
240
+
192
216
240
264
Combination
288
312
336
384
432
GB-28
33.5 (1182)
41.5 (1464)
47.5 (1676)
49.3 (1739)
50.3 (1775)
50.3 (1775)
74 (2611)
50.3 (1775)
90 (3175)
50.3 (1775)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
90 (3175)
High-pressure pipe ø15.88
total length
× 0.11 (kg/m)
Liquid pipe ø6.35 total
length
× 0.024 (kg/m)
Amount (kg)
(to be added for indoor unit)
2.0
2.5
3.0
3.5
4.5
5.0
6.0
8.0
9.0
10.0
12.0
14.0
Amount (kg)
1.5
1.5
3.0
2.5
4.0
3.5
4.0
4.5
4.0
4.5
5.0
2.5
1.5
2.0
2.0
0
0