Descargar Imprimir esta página

Mitsubishi Electric TRANE TURYP0723AN40AN Manual De Instalación página 36

Publicidad

Idiomas disponibles

Idiomas disponibles

・Power cable size and device capacity
MOP is used to select the fuse, switch, or breaker for current leakage.
(1) 208 V
Outdoor unit model
Unit combination
TURYP0723AN40AN/AB
TURYP0963AN40AN/AB
TURYP1203AN40AN/AB
TURYP1443AN40AN/AB
TURYP1683AN40AN/AB
TURYP0963AN40AN/AB
TURYP1923BN40AN/AB
TURYP0963AN40AN/AB
TURYP1203AN40AN/AB
TURYP2163BN40AN/AB
TURYP0963AN40AN/AB
TURYP1203AN40AN/AB
TURYP2403BN40AN/AB
TURYP1203AN40AN/AB
TURYP1443AN40AN/AB
TURYP2643BN40AN/AB
TURYP1203AN40AN/AB
TURYP1443AN40AN/AB
TURYP2883BN40AN/AB
TURYP1443AN40AN/AB
TURYP1683AN40AN/AB
TURYP3123BN40AN/AB
TURYP1443AN40AN/AB
TURYP1683AN40AN/AB
TURYP3363BN40AN/AB
TURYP1683AN40AN/AB
TURYE0723AN40AN/AB
TURYE0963AN40AN/AB
TURYE1203AN40AN/AB
TURYE1443AN40AN/AB
TURYE1683AN40AN/AB
TURYE1923AN40AN/AB
TURYE0963AN40AN/AB
TURYE1923BN40AN/AB
TURYE0963AN40AN/AB
TURYE2163AN40AN/AB
TURYE1203AN40AN/AB
TURYE2163BN40AN/AB
TURYE0963AN40AN/AB
TURYE2403AN40AN/AB
TURYE1203AN40AN/AB
TURYE2403BN40AN/AB
TURYE1203AN40AN/AB
TURYE1443AN40AN/AB
TURYE2643BN40AN/AB
TURYE1203AN40AN/AB
TURYE1443AN40AN/AB
TURYE2883BN40AN/AB
TURYE1443AN40AN/AB
TURYE1683AN40AN/AB
TURYE3123BN40AN/AB
TURYE1443AN40AN/AB
TURYE1683AN40AN/AB
TURYE3363BN40AN/AB
TURYE1683AN40AN/AB
TURYE1923AN40AN/AB
TURYE3843BN40AN/AB
TURYE1923AN40AN/AB
TURYE2163AN40AN/AB
TURYE4323BN40AN/AB
TURYE2163AN40AN/AB
WT09115X03
Minimum size [mm
Power cable
5.3 (10)
8.4 (8)
13.3 (6)
21.2 (4)
21.2 (4)
8.4 (8)
8.4 (8)
13.3 (6)
8.4 (8)
13.3 (6)
13.3 (6)
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
8.4 (8)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
33.6 (2)
13.3 (6)
13.3 (6)
33.6 (2)
21.2 (4)
13.3 (6)
33.6 (2)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
33.6 (2)
33.6 (2)
33.6 (2)
33.6 (2)
(AWG)]
2
Earth leakage breaker
Ground
5.3 (10)
30 A 30 mA or 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
8.4 (8)
40 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
13.3 (6)
50 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
8.4 (8)
35 A 30 mA or 100 mA 0.1 sec. or less
13.3 (6)
45 A 100 mA 0.1 sec. or less
21.4 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
33.6 (2)
80 A 100 mA 0.1 sec. or less
13.3 (6)
45 A 100 mA 0.1 sec. or less
13.3 (6)
45 A 100 mA 0.1 sec. or less
33.6 (2)
100 A 100 mA 0.1 sec. or less
21.4 (4)
60 A 100 mA 0.1 sec. or less
13.3 (6)
45 A 100 mA 0.1 sec. or less
33.6 (2)
100 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
60 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
21.2 (4)
70 A 100 mA 0.1 sec. or less
33.6 (2)
80 A 100 mA 0.1 sec. or less
33.6 (2)
80 A 100 mA 0.1 sec. or less
33.6 (2)
100 A 100 mA 0.1 sec. or less
33.6 (2)
100 A 100 mA 0.1 sec. or less
GB-34
MCA (A)
MOP (A)
24
40
33
50
43
70
52
80
61
100
33
50
33
50
43
70
33
50
43
70
43
70
52
80
43
70
52
80
52
80
61
100
52
80
61
100
61
100
23
35
31
45
41
60
49
80
57
90
66
110
31
45
31
45
73
125
41
60
31
45
82
125
41
60
41
60
49
80
41
60
49
80
49
80
57
90
49
80
57
90
57
90
66
110
66
110
73
125
73
125

Publicidad

loading