Connection: batteries
Requirements:
—The mains fuse provided on site is open.
—The battery fuse on the recharging device has been removed.
—The red (+) and black (-) battery connection cables and the bridge connection can be found in the battery
compartment (condition on delivery).
DANGER
Danger of electrocution!
w
Ensure that the main switch on the AC module is set to position 0 and the fuses on the AC module
and PSU module have been removed.
Connecting the set of batteries (lead-acid gel batteries) for the nBox S
12
1. Insert 1 battery in each battery compartment (no. 1 and 2).
Note
i
·
The battery ports face right.
·
The positive terminal of battery faces forward, while the
negative terminal faces backward.
2. Connect the red battery cable already connected to the
recharging device at terminal BAT.+ to the positive terminal of
battery 1.
3. Connect the black battery cable already connected to the
recharging device at terminal BAT.- to the negative terminal of
battery 2.
4. Use the free third battery cable to connect the negative terminal
of battery 1 to the positive terminal of battery 2.
Note
i
The positive terminal of the battery cable is labelled with a
red heat-shrinkable sleeve and the negative terminal with
a black heat-shrinkable sleeve.
5. Check that cable connections are connected firmly.
6. Record the installation date on the supplied black/silver sticker,
sign the sticker and place on the nBox so it can be seen clearly.