Applying voltage
Checking voltages
DANGER
Danger of electrocution!
If an error occurs, dangerous voltage levels may be present at the system bus terminals and DALI
terminals, which can lead to death or severe injury.
·
Work can only be carried out on the system by authorised personnel wearing appropriate protective
clothing.
·
Relevant health and safety regulations must be observed.
·
In the nBox on the MBC module, terminals CH1 to CH8
Note
i
w
Measure the voltage on the external device that is the furthest away from the nBox.
Voltage
B1 -> B2
> 11.5 V DC
Table 11: Voltage on the system bus
·
nBox MBC
Voltage
DA1 -> DA1
11.5 – 22.5 V DC
DA2 -> DA2
Table 12: Voltage for nBox MBC
Apply voltage: check voltages