Alternative
Piping Methods To
Connect Appliance To Gas Supply
A TRAINED SERVICE
TECHNICIAN
OR GAS
APPLIANCE
INSTALLER
MUST MAKE THE GAS
SUPPLY CONNECTION.
Leak testing of the
appliance
shall be conducted
by the installer
according to the instructions
given,
Unless prohibited by local codes or ordinances, a new
A.G.A. - Certified, flexible metal appliance connector may
be used to connect this appliance to its gas supply. The
connector must be no more than 5 feet in length. Per
figure 5, use appropriate flare union adapter at each end
of the flexible connector. If a flexible connector is used
assure that both the appliance pressure regulator and
manual shut-off valve are joined solidly to other
permanent hard piping (either gas supply or the appliance
manifold) so as to be physically stationary. See
illustrations below.
CAUTION:
D0n0t
attempt tQ attach th e flexibl e
connecto r directly
to an external
pipe
thread.
I
Connection
requires
flare union adapters.
Apply a non-corrosive leak detection fluid to all joints and
fittings in the gas connection between the supply line
shut-off valve and the range. Include gas fittings and
joints in the range if connections were disturbed during
installation. Check for leaks! Bubbles appearing around
fittings and connections will indicate a leak. If a leak
appears, turn off supply line gas shut-off valve, tighten
connections, turn on the supply line gas shut off valve,
and retest for leaks. Never test for gas leaks with an open
flame.
Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 pounds
per square inch (3.5 kPa).
This appliance, as well as its individual shut-off valve,
must be disconnected from the gas supply piping system
during any pressure testing of the system at test
pressures in excess of 1/2 pounds per square inch (3.5
kPa).
When checking appliance regulator function, make certain
pressure of natural gas supply is between 6 and 14
inches of water column or, if converted for LP gas,
between 11 and 14 inches of water column.
ILLUSTRATIVE
ALTERNATIVE
PIPING
Manifold_
Entrance
f_
I
I
-<1--- ppliance Pressure
Regulator,Supplied
(Observedirectionality
of Gas Flow)
I
I_-<1-
Flare Union Adaptor
I
1/2" N.P.T. Flexible
(A5Pf_i.i_nnaCe.)C
° nnect° r
I
" Flare UnionAdaptor
!
- Gas Shut-Off Valve
!
"q1-112" N.RT. Pipe
(Stationary Supply Pipe)
NO APPLIANCE
MOUNTED BELOW
THIS COOKTOP
WALL OVEN MOUNTED
IN CABINETRY BELOW
THIS COOKTOP
FlareUnion
Adaptor
FIGURE5
3/8" N.P.T.
Elbow
3/8" N.P.T.Flexible
ApplianceConnector
(5 ft. max.)
I
I_
-qI- Flare Union
Adaptor
I
-91.- ppliancePressure
Regulator, S upplied
(Observe
directionalityof Gas
I
Flow)
1-1/2" N.P.T.Pipe
Nipple
I
,_ Gas Shut-Off Valve
I
1-1/2" N.P.T.Pipe
(StationarySupply
Pipe)