Descargar Imprimir esta página

Eaton 9PX ModularEasy 6000i Manual De Instalación Y Del Usuario página 17

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 77
4. Power cables connection
This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connection, check that the upstream protection device (Normal AC source) is
open "O" (Off).
Before proceeding to connect the ModularEasy to the UPS, make sure the UPS has been properly shut
down (refer to the UPS user manual).
Always connect the ground wire first.
4.1 9PXMEZ6Ki
1. Connect the 2 power cables of I/O cord Set
the cables and on the UPS I/O cover (blue for UPS Input / red for UPS Output) – refer to the UPS user
manual to check the UPS terminal blocks connection
2. Connect the ModularEasy detection cable from the I/O cord Set
(MBP detect, refer to UPS User Manual "614-09200").
3. Slide the ModularEasy I/O cover
4. Insert the Normal AC source cable through the cable gland
5. Connect the wires to the Normal AC source (Input) terminal blocks
6. Insert the Output cable through the cable gland
7. Connect the wires to the Output terminal blocks
8. Tighten the cable glands
9. Slide back and secure the ModularEasy I/O cover
Page 14
UPS
after removing the screw, to access the ModularEasy terminal blocks
2
to the UPS I/O terminal blocks, following color coding on
1
to the specific UPS connector
1
with the screw
2
614-09354-01_EN

Publicidad

loading

Este manual también es adecuado para:

9px 6000i hotswap9px6kibp9pxmez6ki9pxmez11ki