Installation
Instructions
CABINET PREPARATION CUTOUTS
[]
PREPARING THE COUNTERTOP
The countertopmust have a deep flat surface
to accommodate
the cooktop and the vent.
Countertopswith a rolled front edge and
backsplash may not providethe flat surface
area required.
._t
surface area required
Clearance between
inside front of cabinet and rear
of countertop
cutout must be 20s/a" in order to
accommodate
cooktop
depth.
17_"min.
A 1/2" wide flat area is required around the edge
of opening for support of the unit. The cooktop
unit must be level and sit squarely into countertop
opening.
Carefully cut countertop
opening according
to the dimensions
shown in the illustration.
Be sure
that the opening is cut squarely, with sides parallel
to each other and the rear exactly perpendicular
to the sides.
- 20%"
17_"min.
rsi PREPARING FORDUCTWORK
NOTE:Ductwork MUSTbe vented to outside. DO NOTvent
into a wall, ceiling, crawlspace, attic or ang concealed
space.
Cut hole in cabinet wall or floor as appropriate for gour
installation. Hake sure exhaust duct is located between wall
studs or floor joists.
NOTE:When cutting or drilling into wall or ceiling,
do not damage electrical wiring and other hidden utilities.
g_A"
1B¾"
RearWall Venting
DownwardVenting
[] BLOWERTO DUCTWORK ALIGNMENT
In general,the use of flexible ducting is discouraged because
it can cause severelu restricted airflow. However,if the
blower outlet and the floor or wall duct location do NOTalign
well, then flexible METALductingcan be used to adapt to an
offset. Good alignment without use of flexible ducting is best.
NOTE:
• Do not exceed the maximum recommended offset of 6".
• Do not allow the flexible ducting to kink or collapse.
• Do stretch the flexible ducting as much as possible to
eliminate as much of the corrugation as possible.
to Centerline ZJ
I Is_
LI
,,/"
Offset __
BottomVenting
BackVenting
(Requires 3¼" x 10")
A 3Y4"x 10" rectangle to 6" round transition duct is available
at gour local building supplg store.
NOTE:lllustmtions are for planning purposes only.