5.3. Both Side Ground (BSG)
The BSG (Both Side Grounded)
test mode provides to the user
and to the equipment a safer way
to test objects in a substation
since the both sides of a switch,
contact or circuit breaker is
maintained connected to the
ground during the whole test.
ATTENTION: To perform this procedure, place the auxiliary current clamp
on the ground of the test object before turning on the equipment
1.
Access the device's MENU using the
2.
Use the
confirm.
3.
Use the
to confirm.
4.
Use the
to select ON, and pressing the
5.
Exit the menu and start the test.
6. Protections
The MPK-215R continuous use time is limited by thermal considerations.
Some internal sensors measure the temperature of the sensitive parts
and trigger the protection that will cut the current circulation, if any of them
exceeds the limit temperature, thus avoiding any damage. The
OVERHEATING message will appear in the display. Under these
conditions, measurements will be inhibited up to the temperature
decreases sufficiently.
to select SETUP TEST, and pressing the
to select BOTH SIDE GROUNDED, and pressing the
18
or
button.
to confirm.
to