To maneuver between the Set Clock configuration settings, perform the
following:
1. Within the top level of Configure Instrument, press the ▼ or ▲ key
until Set Clock appears on the display, then press ENTER to configure
the date.
2. Use the ▼ or ▲ keys to view the choices. Press ENTER to make a
selection. Once the format is selected, the display returns to Date
Format
3. Use the ▼ or ▲ keys to navigate to the other date and time options or
press both ▼▲ keys together to return to the top level.
3.3.2. Setup Nameplate
Nameplate values are primary and secondary voltages (or ratios)
associated with a given transformer. This information is available on the
Nameplate of the transformer. The measured results will be compared
with selected (edited) Nameplate values and Deviation will be displayed
and stored in % relative to these values.
The TR8703 allows the storage of 10 Nameplate voltages or ratios which
can be individually selected for a given test.
NOTE:
• The Nameplate list of up to 10 transformers can be written to and
saved only using the software. The values in the list can be edited for
use but cannot be saved from the front panel.
• The keys on the front panel can select any one of the 10 transformer
Nameplate values. Once the transformer values are selected, they can
be edited to a new value using the ▼, ▲ and ENTER keys. When the
new values are selected (even if they are not edited to new values), it
becomes the Present Nameplate and will be used for all subsequent
VT/PT and CT measurements. Deviation will be reported and stored
using these values.
• The Present Nameplate values will be retained in memory even if the
instrument is turned OFF and turned ON. However, it will not be saved
in the list from which it was originally selected.
20