MEGABRAS TR8703 Manual De Uso página 33

Medidor de relación de transformación

Publicidad

Idiomas disponibles

Idiomas disponibles

NOTE:
 If there were a polarity reversal, the Ratio would be displayed negative
and it would be blinking. This means either the connections are
reversed on a given side or the transformer is wound backwards
relative to the marking
 The test may be run as many times as needed by pressing the TEST
button
 An active test can be cancelled at any time by pressing the TEST
button
 Make sure that the H
short to the X
RED
for more connection details
4.2.2. Storing the Measurement Record (Manual and Auto Mode)
The storage mode you are in depends on what you selected when
configuring the instrument (see § 4.3) before running a test.
4.2.2.1. Manual mode
When Manual mode is selected, the Measurement Record storage is
optional to the user.
1. To store the active measurement using Manual mode, press the MEM
(ENTER) button. The display looks as shown below:
2. Select the OBJ and Test location using the ▼ or ▲ key and press
ENTER.
3. Press ENTER or TEST to store the Measurement Record.
NOTE:
 After the test is run, the new location is automatically increased
sequentially from the last stored location.
 If a given location is not available for storage, the Save field will display
N/A.
 In order to NOT STORE the Measurement Record, simply press the
TEST button after the measurement is completed.
lead is always connected such that it does not
RED
or X
lead directly or through earth ground. See § 6
BLACK
34