8.7.3 Condensate drain connection
The condensate forming during heat pump operation flows
through a special drain pipe (1/2"G) that passes inside the insu-
lating casing and comes out at the side of the equipment.
It must be connected, via a trap, to a duct so that the conden-
sate can flow regularly (fig. 64).
fig. 64- Examples of condensate drain connection via a trap
178
EN
8.8
ELECTRICAL CONNECTIONS
The device is equipped with a power cable with Schuko plug to be
connected to the power grid via a suitable socket (fig. 65 and fig. 66).
fig. 65 - Schuko socket
ATTENTION
OBLIGATION
PROHIBITION
ATTENTION
ATTENTION
ATTENTION
ATTENTION
cod. 3540000420 - Rev. 03 - 09/2023
EGEA TECH
The device must be installed in
compliance with the regulations
on electrical systems in force in
the country of installation.
Connect the device to an efficient
grounding system.
Do not use extension cords or
adapters.
For connection to mains and
safety devices, comply with the
IEC 60364-4-41 standard.
DO NOT TAMPER WITH THE
POWER CORD.
If the power supply cable is dam-
aged, it must be replaced by the
manufacturer or the technical as-
sistance service or in any case
by a person with similar qualifica-
tions, in order to prevent any risk.
If the equipment is electrically po-
wered, do not touch it with bare
feet or with wet parts of the body.
All power circuits must be di-
sconnected before accessing the
electrical panel of the appliance.
200 HT - 260 HT
fig. 66 - Unit plug