6.
To complete the First start assist-
ant, select the values and settings
when prompted by the assistant.
Continue until the panel shows
that the first start is complete.
When the panel shows that the
first start is complete, the drive
is ready for use. Press
to enter the Home view.
Motor overload protection
Motor overload protection is not enabled by default. Motor overload protection can
be measured or estimated in one of the following ways: 1) using motor temperature
devices, 2) using a motor model defined by parameters, or 3) using motor current and
motor class curves. To enable protection using motor temperature devices or motor
model parameters, set parameter 35.11 and subsequent parameters through 35.55.
To adjust motor class curves (default is class 20), change parameters 35.56 and 35.57.
Use the information key (
group 35 parameters. You must set the drive overload parameters correctly, or motor
damage can occur.
Fieldbus communication
To configure the embedded fieldbus communication for BACnet MSTP, you must set
at least these parameters:
Parameter
Setting
20.01 Ext1 commands
Embedded fieldbus
22.11 Speed ref1 source
EFB ref1
26.11 Torque ref1 source
EFB ref1
28.11 Frequency ref1
EFB ref1
source
58.01 Protocol enable
BACnet MSTP
58.03 Node address
1 (default)
58.04 Baud rate
19.2 kbps (default)
58.05 Parity
8 EVEN 1 (default)
7.
The Home view monitors the val-
ues of selected signals.
(Done)
?
) on the drive control panel for more information on setting
Description
Selects fieldbus as the source for the start and stop
commands when EXT1 is selected as the active control
location.
Selects a reference received through the embedded
fieldbus interface as speed reference 1.
Selects a reference received through the embedded
fieldbus interface as torque reference 1.
Selects a reference received through the embedded
fieldbus interface as frequency reference 1.
Initializes embedded fieldbus communication.
Node address. There must be no two nodes with the
same node address on-line.
Defines the communication speed of the link. Use the
same setting as in the master station.
Selects the parity and stop bit setting. Use the same
setting as in the master station.
EN – Quick installation and start-up guide 19
8.
Make additional adjustments
starting from the Main menu.
Press
(Menu) in the Home
view to enter the Main menu.
Select Primary settings and press
(Select).
To get more information on the
Primary settings menu items,
?
press
to open the help page.