6. Electrical work
A
B
~208/230 V
A
~208/230 V
Fig. 6-2
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
~ 208/230 V
Indoor
unit 1
Indoor unit
PLFY-NEMU, PMFY-NBMU, PEFY-NMSU, PCFY-NKMU,
Type 1
PKFY-NHMU, PKFY-NLMU, PKFY-NKMU, PLFY-NFMU
Type 2
PEFY-NMAU
Type 3
PEFY-NMHSU
Others
Other indoor unit
• V1 and V2
V1 and V2 are the breaker coefficient.
V1: Breaker coefficient of rated current
V2: Breaker coefficient of current sensitivity
The values of V1 and V2 differ from depending on the model. Therefore, please refer to IM of each model.
• C : Multiple of tripping current at tripping time 0.01 s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
• Condition PEFY-NMSU × 4 + PEFY-NMAU × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
<Example of "G1" calculation>
*Condition : PKFY-NLMU × 2 + PLFY-NEMU × 2 + PEFY-NMAU × 1
V2 of PKFY-NLMU = 2.4, V2 of PLFY-NEMU = 2.4, V2 of PEFY-NMAU = 1.6, Wire thickness and length: 1.5 mm
G1 = 2.4 × 2 + 2.4 × 2 + 1.6 × 1 + 48 × 0.2
= 20.8
As a result , current sensitivity is 30 mA 0.1 sec or less.
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
2
1.5 mm
, AWG14
2
2.5 mm
, AWG13
2
4.0 mm
, AWG11
D
C
C
C
C
C
B
D
L1 L2
M1
M2
S
1 2
C
TB2
TB5
TB15
Minimum wire thickness (mm², AWG.No)
Main cable
Branch
1.5, AWG14
1.5, AWG14
2.5, AWG13
2.5, AWG13
4.0, AWG11
4.0, AWG11
Indoor
Indoor
Indoor
unit 1
unit 2
unit 3
V1
19.8
38
13.8
0
V3
48
56
66
6.2. Power supply wiring
• Wiring size must comply with the applicable local and national codes.
• Use copper supply wires.
Use UL wires rated 300 V or more for the power supply cords.
• Install a ground wire longer than other cables.
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 6-2]
A
Ground-fault interrupter
B
Local switch/Wiring breaker
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
Ground-fault interrupter *1
Ground
1.5, AWG14
20 A current sensitivity *3
2.5, AWG13
30 A current sensitivity *3
4.0, AWG11
40 A current sensitivity *3
Indoor
unit 3
V2
2.4
1.6
4.8
0
Local switch (A)
Breaker for wiring
(NFB)
Capacity
Fuse
16
16
25
25
32
32
Sample chart
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
Rated Tripping current (x)
2
(AWG14) 0.2 km
20
30
40
8
10
20
C
en
15