6. Electrical work
A
ON
OFF
1 2 3 4 5 6 7 8 9 10
SW12
0
ADDRESS
Fig. 6-4
6.7. Electrical characteristics
Model
PKFY-WL04NLMU-E
PKFY-WL06NLMU-E
PKFY-WL08NLMU-E
208/230 V / 60 Hz
PKFY-WL12NLMU-E
PKFY-WL15NLMU-E
SWA
CN43
CN82
SW1
SW11
SW14
0
0
Power supply
Volts / Hz
Range ± 10%
Max.: 253 V
Min.: 198 V
6.5. Setting addresses (Fig. 6-4)
(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match SW11
(for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
6.6. Sensing room temperature with the built-in
sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote
controller, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-
8 as necessary also makes it possible to adjust the air flow at a time when the
heating thermometer is OFF.
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
MCA (A)
Output (kW)
0.24
0.24
0.24
0.24
0.24
FLA: Full Load Amps
Output: Fan motor rated output
IFM
FLA (A)
0.03
0.19
0.03
0.19
0.03
0.19
0.03
0.19
0.03
0.19
en
17