01: Output voltage setting 
Interface 
02: Frequency Converter enable/disable 
Interface 
03: Output frequency setting 
Interface 
04: ECO enable/disable 
Interface 
05: ECO voltage range setting 
Interface 
 
www.powerwalker.com 
Setting 
Parameter 3: Output voltage 
For 208/220/230/240 VAC models, you may choose the 
following output voltage: 
208: presents output voltage is 208Vac 
220: presents output voltage is 220Vac 
230: presents output voltage is 230Vac 
240: presents output voltage is 240Vac 
For 110/150/120/127 VAC models, you may choose the 
following output voltage: 
 
110: presents output voltage is 110Vac 
115: presents output voltage is 115Vac 
120: presents output voltage is 120Vac 
127: presents output voltage is 127Vac 
Setting 
Parameter 2 & 3: Enable or disable converter mode. You may 
choose the following two options: 
CF ENA: converter mode enable 
CF DIS: converter mode disable 
 
Setting 
Parameter 2 & 3: Output frequency setting.   
You may set the initial frequency on battery mode: 
BAT 50: presents output frequency is 50Hz 
BAT 60: presents output frequency is 60Hz 
If converter mode is enabled, you may choose the following 
output frequency: 
 
CF 50: presents output frequency is 50Hz 
CF 60: presents output frequency is 60Hz 
Setting 
Parameter 3: Enable or disable ECO function. You may choose 
the following two options:   
ENA: ECO mode enable 
DIS: ECO mode disable 
 
Setting 
Parameter 2 & 3: Set the acceptable high voltage point and 
low voltage point for ECO mode by pressing Down key or Up 
key.     
HLS: High loss voltage in ECO mode in parameter 2. 
For 208/220/230/240 VAC models, the setting range in 
parameter 3 is from +7V to +24V of the nominal voltage. 
 
For 110/115/120/127 VAC models, the setting range in 
Page 11