06: Bypass enable/disable when UPS is off
Interface
07: Bypass voltage range setting
Interface
08: Programmable outlets enable/disable
Interface
09: Programmable outlets setting
Interface
00: Exit setting
www.powerwalker.com
parameter 3 is from +3V to +12V of the nominal voltage.
LLS: Low loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range in
parameter 3 is from ‐7V to ‐24V of the nominal voltage.
For 110/115/120/127 VAC models, the setting voltage in
parameter 3 is from ‐3V to ‐12V of the nominal voltage.
Setting
Parameter 3: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable
Setting
Parameter 2 & 3: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high voltage point
For 208/220/230/240 VAC models:
230‐264: setting the high voltage point in parameter 3 from
230Vac to 264Vac.
For 110/115/120/127 VAC models:
120‐132: setting the high voltage point in parameter 3 from
120Vac to 132Vac
LLS: Bypass low voltage point
For 208/220/230/240 VAC models:
170‐220: setting the low voltage point in parameter 3 from
170Vac to 220Vac
For 110/115/120/127 VAC models:
85‐115: setting the low voltage point in parameter 3 from
85Vac to 115Vac.
Setting
Parameter 3: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable
Setting
Parameter 3: Set up backup time limits for programmable
outlets.
0‐999: setting the backup time limits in minutes from 0‐999 for
programmable outlets which connect to non‐critical devices on
battery mode.