3‐6. Operating Mode Description 
Operating mode 
Description 
Online mode 
When the input voltage is within 
acceptable range, UPS will provide pure 
and stable AC power to output. The UPS 
will also charge the battery at online mode. 
ECO mode 
Energy saving mode:   
When the input voltage is within voltage 
regulation range, UPS will bypass voltage to 
output for energy saving.   
Frequency 
When input frequency is within 40 Hz to 70 
Converter mode 
Hz, the UPS can be set at a constant output 
frequency, 50 Hz or 60 Hz.    The UPS will 
still charge battery under this mode. 
Battery mode 
When the input voltage is beyond the 
acceptable range or power failure and 
alarm is sounding every 4 second, UPS will 
backup power from battery.   
Bypass mode 
When input voltage is within acceptable 
range but UPS is overload, UPS will enter 
bypass mode or bypass mode can be set by 
front panel. Alarm is sounding every 10 
second.   
Standby mode 
UPS is powered off and no output supply 
power, but still can charge batteries. 
 
3‐7. Faults Reference Code 
Fault event 
Bus start fail 
Bus over 
Bus under 
Bus unbalance 
Inverter soft start fail 
Inverter voltage high 
 
www.powerwalker.com 
Fault code   
Icon 
Fault event 
01 
Inverter voltage Low 
02 
Inverter output short 
03 
Battery voltage too high 
04 
Battery voltage too low 
11 
Over temperature 
12 
Over load 
Page 13
LCD display   
Fault code   
13 
14 
27 
28 
41 
43 
EN
Icon 
 