Specifications
Model
Nominal voltage
and input range:
Nominal input frequency
and tolerance:
Nominal output
voltage:
Nominal output
frequency:
Output voltage
regulation in line mode:
Output voltage
regulation in battery
mode:
Nominal output
power in W / VA:
Output voltage
waveform:
Maximum output
current @ P . F.
Maximum harmonic
distortion of output
voltage at full resistive
load
Efficiency with nominal
load:
Maximum operating
altitude at 100% of
nominal power:
Online overload
capability:
Overload capacity in
battery mode:
Current limitation:
Autonomy time at
full load:
Battery recharge time:
Transfer time:
Outlets:
Maximum input current:
21-10-012 - 933148-Book.indb 20
21-10-012 - 933148-Book.indb 20
SMART1000RMXL2U
120V~, 83-147V~
60 Hz (+/- 5 Hz)
120V~ sinusoidal in
line mode and 120V~
sinusoidal in battery
mode
60 Hz (+/- 0.5 Hz)
120V~ (+6% / -
14%)
120V~ (+/-5%)
900W / 1000VA
Sinusoidal in line
mode and sinusoidal
in battery mode
8.3A @ 120V~
P .F. = 0.9
3%
95%
6561 ft. (2000 m)
125% for 10 minutes
105% @ 0.5 seconds
Input 15A
6.32 minutes @
900W
4.5 hours
4 milliseconds typical
(4 milliseconds max)
8x 5-15R outlets
with battery backup,
regulation and surge
9.2A
20
SMART1500RM2U
SMART1500RMXL2UA
120V~, 83-147V~
60 Hz (+/- 5 Hz)
120V~ sinusoidal
in line mode and
line mode and 120V~
120V~ sinusoidal in
battery mode
60 Hz (+/- 0.5 Hz)
120V~ (+6% / -
120V~ (+6% / - 14%)
14%)
120V~ (+/-5%)
1350W / 1500VA
Sinusoidal in line
mode and sinusoidal
mode and sinusoidal in
in battery mode
12A @ 120V~
P .F. = 0.9
3%
95%
6561 ft. (2000 m)
125% for 10
minutes
105% @ 0.5
105% @ 0.5 seconds
seconds
Input 15A
4.45 minutes @ 1
350W
4.5 hours
5 milliseconds
typical (5
milliseconds max)
8x 5-15R outlets
with battery backup,
regulation and surge
12A
120V~, 83-147V~
60 Hz (+/- 5 Hz)
120V~ sinusoidal in
sinusoidal in battery
mode
60 Hz (+/- 0.5 Hz)
120V~ (+/-5%)
1350W / 1400VA
Sinusoidal in line
battery mode
12A @ 120V~
P .F. = 0.9
3%
95%
6561 ft. (2000 m)
125% for 10 minutes
Input 15A
4.85 minutes @ 1
350W
4.5 hours
5 milliseconds typical
(5 milliseconds max)
8x 5-15R outlets
with battery backup,
regulation and surge
12A
10/14/2021 1:10:30 PM