5.2 ELECTRICAL CONNECTIONS FOR 230V MODELS
In case you have to operate on the control panel (for wiring, adjustments etc...), remove the circuit support plate. To do this, pro-
ceed as follows (Picture 12):
•
unscrew the fixing screws of the control panel holder plate, without removing them;
•
Unhook the plate of the barrier case as shown;
•
Move the control panel box into a most comfortable position and perform the necessary tasks;
Execute the wiring following the directions of "Table 2" and diagrams on page 25.
WARNING To ensure an appropriate level of electrical safety always keep the 230V power supply cables apart (minimum 4mm
in the open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial and auxiliary
circuits power supply), and fasten the latter with appropriate clamps near the terminal boards.
WARNING Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure
multi pole disconnection from the power supply, with a contact opening of 3 mm.
WARNING To connect the encoder to the control panel, use only a dedicated cable 3x0,22mm
1-2
230 V ~ ±10% (50/60 Hz) power supply input
3-4-5
Operator 1 output 230 V ~ max 600W
6-7-8
Operator 2 output 230 V ~ max 600W (if present)
9-10
230 V ~ max 100 W output for open gate warning light (if P052=0) or courtesy light (if P052>1)
11-12
Flashing light output 230 V ~ max 40W
Electric-lock output max 1 art. 110 (if P062=0), 24V
13-14
brake output for reversible motors (if P062=3)
15-16
Led flashing light output max 1 art. LED24AI (24 V
17 - N.O.
17-18
18 - Com
19 - N.O.
19-20
20 - Com
21 - N.O.
21-22
22 - Com
23 - N.O.
23-24
24 - Com
25 - N.C.
25-26
26 - Com
27 - N.O.
27-28
28 - Com
29
Aerial signal input
30
Ground aerial input
31-32
+24 V
24
Tabella 2 "collegamento alle morsettiere"
Input 6. Unused.
Input 5. Unused.
Input 4. Unused.
Input 3. Unused.
Input 2 PHOTO 1. When enabled (see parameter P050 in the table), activation of
PHOTO 1 provokes: an inversion of direction (during closing), the arrest of the mo-
vement (during opening), prevent the start (gate closed). If unused, short circuit.
Input 1 START. In case of intervention it provokes: the operator opening or closing. It
may operate as "inversion" mode (P49=0) or "step by step" mode (P49=1).
power supply output for auxiliary devices 200mA
.
2
output max 5W configurable (if P062≠0) or electro-
max 100 mA)