Setup pH
The Setup pH menu consists of six (6) sub-menus:
• Setpoint pH: 7.4pH (range 6-8pH) Set the pH value keep in the pool.
• Setpoint Type: Acid (Acid/Alkaline) Type dosing product to regulate the
pH value. Acid: add chemical Acid product, Alka: add chemical Alkaline
product.
• Temperature: 25°C (Automatic compensation by manual value or set
Automatic to use an external temperature sensor)
• OFA Alarm: Over Feed alarm value in minutes value (OFF...60'), it is a
maximum relay time activation.
• Alarm Min: Setting the minimum pH alarm value (0,0...6,0 pH)
• Alarm Max: Setting the Maximum pH alarm value (8,0...14,0 pH)
• *Time ON: range from 5'' to 360'' (Default Time ON: 180'')
• *Time OFF: range from 5'' to 360'' (Default Time OFF: 360'')
*Notes:
The items Time ON and Time OFF will be displayed if the Timed dosing method
is set in the Advanced menu.
Time OFF must be equal to or greater than Time ON.
Scroll through the menu using
Setup ORP
The Setup ORP menu consists of five (5) sub-menus:
• Setpoint ORP: 700mV (range 400-850mV) Set the ORP value keep in the
pool.
• Setpoint Type: Low (LOW/HIGH) Type of dosing regulation. Low: add
chemical chlorine, High: reduce chemical chlorine.
• OFA Alarm: Over Feed alarm value in minutes value (OFF...60'), it is a
maximum relay time activation.
• Alarm Min: Setting the minimum ORP alarm value (0...600 mV)
• Alarm Max: Setting the Maximum ORP alarm value (800...1000 mV)
• *Time ON: range from 5'' to 360'' (Default Time ON: 180'')
• *Time OFF: range from 5'' to 360'' (Default Time OFF: 360'')
*Notes:
The items Time ON and Time OFF will be displayed if the Timed dosing method
is set in the Advanced menu.
Time OFF must be equal to or greater than Time ON.
EasyChem Double and Plug version | pH · ORP
g
g
, select the item and confirm with
Only use spare parts supplied by Hayward brands ®
SETUP
PH
SETPOINT PH
SETPOINT TYPE
ACID (pH-)
TEMPERATURE
OFA ALARM
.
ALARM MIN
ALARM MAX
TIME ON
TIME OFF
SETUP
ORP
SETPOINT ORP
SETPOINT TYPE
OFA ALARM
Page 11 on 27
7.4pH
25°C
OFF
6.0pH
8.0pH
180"
360"
700mV
LOW