5
USER SET MENU
Access to the list of parameters on entering the user menu:
N.
Code
U00
StA
U01
StF
Cooling setpoint (°C)
U02
bnF
Cooling band (°C)
U03
StC
Heating setpoint (°C)
U04
bnC
Heating band (°C)
U05
CSt
Correction set
U06
SF1
Cooling setpoint 1 (°C)
Outside air temperature at
U07
tF1
U08
SF2
Cooling setpoint 2 (°C)
Outside cooling air
U09
tF2
temperature 2 (°C)
U10
SC1
Heating setpoint 1 (°C)
Outside heating air
U11
tC1
temperature 1 (°C)
U12
SC2
Heating setpoint 2 (°C)
Outside heating air
U13
tC2
temperature 2 (°C)
U14
SAS
Domestic water setpoint (°C)
U15
bAS
Domestic water band (°C)
20
Name
Min
Default
Season
0
0
5.0
7.0
0.0
5.0
25.0
45.0
0.0
5.0
0
0
-30.0
12.0
-30.0
18.0
cold 1 (°C)
-30.0
7.0
-30.0
30.0
-30.0
45.0
-30.0
0
-30.0
35.0
-30.0
18.0
25.0
70.0
0.0
10.0
Max
If 0 - the machine works in cold mode, unless the contact operating mode is forced.
If 1 - works in hot mode. If this parameter is changed while the machine is
1
operating, it is automatically switched off and switched on again with the
operating mode selected.
20.0
Setpoint temperature used in the cooling mode
20.0
Temperature band used with cooling mode
Setpoint temperature used in the heating mode:
The maximum limit can be configured using the parameter(t) in the menu with
Parameter N23
PSW=30;
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint entry to
adjust the boiler.
20.0
Temperature band used with heating mode
Parameter indicating activation of set correction based on outside temperature:
0: no correction on set
1: correction on set in the cooling mode
3
2: correction on set in the heating mode
3: correction on heating and cooling set
The setpoint is calculated every 30 min
Visible only with the setpoint correction enabled. Set to cold 1 = temperature as
145.0
per parameter 7
Visible only with the setpoint correction enabled. Outside air temperature 1
145.0
corresponds to set at cold 1 parameter 6
Visible only with the setpoint correction enabled. Set to cold 2 = temperature as
145.0
per parameter 9
Visible only with the setpoint correction enabled. Outside air temperature 2
145.0
corresponds to set at cold 2 parameter 8
Visible only with the setpoint correction enabled. Set to hot 1. Set to hot used as
first extreme between which the set can be changed:
The maximum limit can be configured using the parameter(t) in the menu with
145.0
PSW=30;
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint entry to
adjust the boiler.
Visible only with the setpoint correction enabled. Outside air temperature
145.0
corresponds to set at hot 1 (parameter A)
Visible only with the setpoint correction enabled. Set to hot 2. Set to hot used as
second extreme between which the set can be changed.
The maximum limit can be configured using the parameter(t) in the menu with
145.0
PSW=30;
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint entry to
adjust the boiler.
Visible only with the setpoint correction enabled. Outside air temperature
145.0
corresponds to set at hot 2 (parameter C)
Setpoint temperature used when the production of domestic water is enabled:
The maximum limit can be configured using the parameter(t) in the menu with
Parameter N23
PSW=30;
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint entry to
adjust the boiler.
20.0
Temperature band used with the domestic water mode setpoint.
Meaning