AERMEC ANKI Manual De Uso página 23

Regulación electrónica

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

N.
Code
Name
N28
tA1
Outside air setpoint 1 (°C)
N29
tA2
Outside air setpoint 2 (°C)
N30
ba
Air band (°C)
Minimum Power in domestic
N31
PAS min
hot water mode (%)
Maximum Power in
N32
PAS max
domestic hot water mode
(%)
N33
OffP
Thermostat pump switch-off
N34
VP
Fixed pump volts
N36
Type of multi-function input
Minimum NTC probe multi-
N37
function input value
Maximum NTC probe multi-
N38
function input value
N39
Minimum Volts 0-10V
N40
Maximum Volts 0-10V
N41
Min demand limit value
N42
Max demand limit value
N43
Min cold setpoint value
N44
Max cold setpoint value
N45
Min hot setpoint value
N46
Max hot setpoint value
System storage tank
N47
SetPoint
N48
System storage tank band
Minimum domestic hot
N49
water setpoint offset
Maximum domestic hot
N50
water setpoint offset
Countdown to next
N51
defrosting
Cooling system storage tank
N52
SetPoint
N53
Max. force off time (min)
N54
UoM UI
N55
UoM BMS
N56
UoM LOG
Min
Default
Max
Below this threshold, the supplementary heater thermostat is activated (it comes
-30.0
5.0
70.0
on at Sri and switches off at Sri+bri).
Under this threshold, only the operation of the heater is enabled, not the one of
-30.0
-30.0
70.0
the compressor.
0.0
2.0
20.0
Band to be applied to the air temperature setpoints.
For units envisaging the domestic hot water production function, once this
0
50
100
function has been activated, it is possible to decide the minimum power
percentage to be used in order to produce domestic hot water.
For units envisaging the domestic hot water production function, once this
0
70
100
function has been activated, it is possible to decide the maximum power
percentage to be used in order to produce domestic hot water.
0: the pump remains in operation when the setpoint temperature is reached.
1: the pump is switched off when the setpoint temperature is reached. (when this
option is selected, the adjustment is activated automatically in relation to the input
temperature).
0
0
1
This parameter is only displayed when adjustment based on input temperature
(parameter(0) =1 or 2). The input water temperature probe can be a remote unit
at 50m from the exterior of the machine in order to measure the temperature of a
storage tank.
Fixed volts for inverter pump on-board the machine. Can be set in relation to plant
0.0
10.0
10.0V
features (see pump documentation).
0: NTC input
0
0
1
1: 0-10V input
Minimum value which must be matched by the final result in relation to the
-30.0
0.0
70.0
configuration of the multi-function input. See parameter N11.
Maximum value which must be matched by the final result in relation to the
-30.0
20.0
70.0
configuration of the multi-function input. See parameter N11.
Minimum volts which must be matched by the final result in relation to the
0.0
0.0
10.0V
configuration of the multi-function input. See parameter N11.
Maximum volts which must be matched by the final result in relation to the
0.0
10.0
10.0V
configuration of the multi-function input. See parameter N11.
Minimum demand limit value which must be matched by the minimum value set
0.0
0.0
100.0%
for the multifunction input in relation to the type of analogue input set.
Maximum demand limit value which must be matched by the maximum value of
0.0
100.0
100.0%
the multifunction input in relation to the type of analogue input set.
Minimum cold setpoint value which must be matched by the minimum value set
-30.0
7.0
145°C
for the multifunction input in relation to the type of analogue input set.
Maximum cold setpoint value which must be matched by the minimum value set
-30.0
12.0
145°C
for the multifunction input in relation to the type of analogue input set.
Minimum hot setpoint value which must be matched by the minimum value set for
-30.0
40.0
145°C
the multifunction input in relation to the type of analogue input set.
Maximum hot setpoint value which must be matched by the minimum value set
-30.0
45.0
145°C
for the multifunction input in relation to the type of analogue input set.
Storage tank setpoint when multi-function input is configured as a remote probe
-30.0
45.0
145°C
on the storage tank.
Adjustment band using remote probe on system storage tank when the multi-
0.0
5.0
20.0
function input is configured.
Minimum offset to be applied to the domestic hot water setpoint when the
0.0
0.0
20.0
function is configured through the multi-function input.
Maximum offset to be applied to the domestic hot water setpoint when the
0.0
0.0
20.0
function is configured through the multi-function input.
Read-only parameter, displays the time remaining to the start of the next
defrosting. (if all other defrosting conditions are met).
Storage tank setpoint when multi-function input is configured as a remote probe
-30.0
7.0
70°C
on the storage tank.
Maximum dwell time in force-off state (both heating and cooling), after which the
5
20
150
compressor is allowed to restart.
Enabling conversion of units of measurement, Celsius (°C) to Fahrenheit (°F) and
0
0
1
bar (bar) to psi (psi) regarding the display.
Enabling conversion of units of measurement, Celsius (°C) to Fahrenheit (°F) and
0
0
1
bar (bar) to psi (psi) regarding the supervision.
Enabling conversion of units of measurement, Celsius (°C) to Fahrenheit (°F) and
0
0
1
bar (bar) to psi (psi) regarding the LOG registration.
Meaning
23