Dimensions And Service Space; Inspecting, Handling And Unpacking The Unit; Mounting The Indoor Unit - Daikin EKHBH030BA Manual De Instalación

Unidad interior para bomba de calor de aire-agua
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Dimensions and service space

Unit of measurement: inch (mm)
Dimensions of the unit, see figure 3
1
Flexible drain hose
2
Water outlet connection
3
Water inlet connection
4
Refrigerant liquid
connection
Required service space, see figure 2

Inspecting, handling and unpacking the unit

The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet.
At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent.
Check if all indoor unit accessories (see "Accessories" on
page 2) are enclosed.
Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during
transport.
The indoor unit weighs approximately 102 lbs (46 kg) and
should be lifted by two persons using the two lifting bars
provided.
CAUTION
Do not grasp the switch box or piping to lift the unit! Two
lifting bars are provided to lift the unit.
EKHBH/X030BA
Indoor unit for air to water heat pump system
4PW62568-1 – 07.2010
5
Refrigerant gas
connection
MBSP
Male British Standard
Pipe

Mounting the indoor unit

CAUTION
The weight of the indoor unit is approximately 102 lbs
(46 kg). Two persons are required to mount the unit.
1
Put the installation pattern (see packing) on the wall and mark
the fixation positions (2 on top ( T) and 2 at the bottom (
Make sure that the marks (2 by 2) are completely level and the
dimensions of the marks are corresponding according to
figure 4 (unit of measurement: inch (mm)).
When the unit is not installed level, air might get trapped in the
water circuit resulting in malfunctioning of the unit.
Pay special attention to this when installing an EKHBX model to
prevent overflow of the drain pan.
2
Drill 4 holes and install 4 plugs (suitable for M10).
3
Put the screws in top plugs and hang the indoor unit on the top
screws.
4
Put the screws in bottom plugs and fix the screws firmly.
2
1
1
B)).
3
4
Installation manual
13

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Ekhbx030baEkhbh054baEkhbx054ba

Tabla de contenido