Typical Application Examples; Application 1; Application 2 - Daikin EKHBH030BA Manual De Instalación

Unidad interior para bomba de calor de aire-agua
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

T
YPICAL APPLICATION EXAMPLES
The application examples given below are for illustration purposes
only.

Application 1

Space heating only application with the room thermostat connected
to the indoor unit.
T
1
2
3
4
5
7
1
Outdoor unit
2
Indoor unit
3
Heat exchanger
4
Pump
5
Shut-off valve
Pump operation and space heating
When the room thermostat (T) is connected to the indoor unit, the
pump (4) will operate when there is a heating request from the room
thermostat, and the outdoor unit will start operating to achieve the
target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the
outdoor unit and pump will stop operating.
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 19) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 23).
Installation manual
4
6
FHL1
FHL2
FHL3
6
Collector (field supply)
7
Shut-off valve
FHL1..3
Floor heating loop
T
Room thermostat
(optional)

Application 2

Space heating only application without room thermostat connected to
the indoor unit. The temperature in each room is controlled by a valve
on each water circuit. Domestic hot water is provided through the
domestic hot water tank which is connected to the indoor unit.
1
2
3
4
5
8
M
7
1
Outdoor unit
2
Indoor unit
3
Heat exchanger
4
Pump
5
Shut-off valve
6
Collector (field supply)
7
Shut-off valve
8
Motorised 3-way valve
(delivered with
domestic hot water
tank)
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
NOTE
Details on pump configuration can be found under
"Pump operation configuration" on page 23.
Space heating
The outdoor unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.
When circulation in each space heating loop (FHL1..3)
NOTE
is controlled by remotely controlled valves (M1..3), it is
important to provide a by-pass valve (9) to avoid the
flow switch safety device from being activated.
The by-pass valve should be selected as such that at
all time the minimum water flow as mentioned under
"Water pipework" on page 14 is guaranteed.
It is recommended to select a pressure difference
controlled by-pass valve.
Indoor unit for air to water heat pump system
6
T1
T2
T3
M1
M2
M3
11
12
FHL1
FHL2
FHL3
10
9
By-pass valve
(field supply)
10
Domestic hot water tank
(optional)
11
Booster heater
12
Heat exchanger coil
FHL1..3
Floor heating loop
T1..3
Individual room
thermostat (optional)
M1..3
Individual motorised
valve to control loop
FHL1 (field supply)
EKHBH/X030BA
4PW62568-1 – 07.2010
9

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Ekhbx030baEkhbh054baEkhbx054ba

Tabla de contenido