[8] Domestic water heating mode timer
Applies only to installations with a domestic hot water tank.
The 'domestic water heating mode timer' field settings defines the
minimum and maximum domestic water heating times, minimum time
between two domestic water heating cycles by heat pump, and
booster heater delay time.
[8-00] Minimum running time: specifies the minimum time
period during which heat pump domestic water heating mode
should be activated, even when the target domestic hot water
temperature for heat pump (T
reached.
[8-01] Maximum running time: specifies the maximum time
period during which heat pump domestic water heating mode
can be activated, even when the target domestic hot water
temperature for heat pump (T
reached.
The actual maximum running time will automatically variate
between [8-01] and [8-01]+[8-04] depending on the outdoor
temperature. See figure in chapter "[8-04]" on page 32.
Note that when the unit is configured to work with a
room thermostat (refer to "Room thermostat
installation
configuration"
maximum running timer will only be taken into
account when there is a request for space cooling
or space heating. When there is no request for
room cooling or room heating, domestic water
heating by the heat pump will continue until the
'heat pump OFF temperature' (see field settings [6]
on page 29) is reached. When no room thermostat
is installed, the timer is always taken into account.
[8-02] Anti-recycling time: specifies the minimum required
interval between two heat pump domestic water heating
mode cycles.
The actual anti-recycling time will automatically variate
between [8-02] and 0 depending on the outdoor temperature.
See figure in chapter "[8-04]" on page 32.
1
0
1
0
[8-00]
[8-01]
1
Heat pump domestic water heating mode
(1 = active, 0 = not active)
2
Hot water request for heat pump (1 = request, 0 = no request)
t
Time
If the outdoor temperature is higher than the field setting to
which parameter [4-02] is set, then field settings of
parameters [8-01], [8-02], and [8-04] are not considered.
EKHBH/X030BA
Indoor unit for air to water heat pump system
4PW62568-1 – 07.2010
) has already been
HP OFF
) has not yet been
HP OFF
on
page 23),
the
t
[8-02]
[8-03] Booster heater delay time: specifies the start-up time
delay of the booster heater operation when heat pump
domestic water heating mode is active.
When heat pump is active in domestic water
heating mode, the delay time of booster
heater is [8-03].
When heat pump is not active in domestic
water heating mode, the delay time is 20 min.
The delay timer starts from booster heater ON
temperature (T
1
4
0
1
3
0
1
0
1
0
[8-03]
1
Booster heater operation (1 = active, 0 = not active)
2
Heat pump domestic water heating mode
(1 = active, 0 = not active)
3
Hot water request for booster heater
(1 = request, 0 = no request)
4
Hot water request for heat pump (1 = request, 0 = no request)
t
Time
By adapting the booster heater delay time versus the
maximum running time, an optional balance can be
found between the energy efficiency and the heat up
time.
However, if the booster heater delay time is set too
high, it might take a long time before the domestic hot
water reaches its set temperature upon domestic hot
water mode request.
The purpose of [8-03] is to delay the booster heater in
relation with the heat pump operation time in domestic
water heating mode.
The setting [8-03] has only meaning if setting
[4-03]=1. Setting [4-03]=0/2/3 limits the booster
heater automatically in relation to heat pump
operation time in domestic water heating mode.
Take care that [8-03] is always in relation with the
maximum running time [8-01].
Example: [4-03]=1
Energy saving settings
[8-01]
20~60 min
[8-03]
[8-01] + 20 min
)
BH ON
t
Quick heating settings
(default)
30 min
20 min
Installation manual
31