Motor and Phase Rotation Indicator/English
Note
The bottom of the Motor and Phase Rotation Indicator should be
oriented towards the drive shaft. See the Orientation Symbol on the
Motor and Phase Rotation Indicator.
Either the Clockwise or Counter Clockwise Rotary indicator Illuminates
showing the type of rotary field direction present.
Magnetic Field Detection
To detect a magnetic field, place the Motor and Phase Rotation Indicator
to a solenoid valve.
A magnetic field is present if either the Clockwise or the Counter
Clockwise Rotary indicator illuminate.
Unpacking the Motor and Phase Rotation Indicator
The Motor and Phase Rotation Indicator ships with the following items:
3 test leads
3 test probes
3 alligator clips
9 V battery
Users Manual
Specifications
Environmental
Operating Temperature:0℃ to +40℃
Operating Altitude: 2000 m
Pollution Degree: 2
Type of protection: IP 40
Mechanical Specifications
Size (H x W x D): 130mm x 69mm x 32mm.
Weight: 130g
Humidity:15% to 80%
Safety Specifications
6
Electrical Safety:
Meets IEC 61010 IEC 61557-7 / EN61557-7
Maximum Operating Voltage (Ume):400 V AC for all ranges
Protection Levels: CAT III, 300V
Measure
ment
Application
Category
Measurements on circuits not directly connected to mains.
Examples
include:
Ⅰ
equipment and specially protected (internal) mains-derived
circuits.
Measurements on circuits directly connected to the low voltage
installation.
Ⅱ
Examples include: Household appliances, portable tools and
similar equipment.
Measurements performed in the building installation.
Examples include measurements on distribution boards,
Ⅲ
junction boxes, socket-outlets and wiring and cables in the fixed
installation.
Measurements performed at the source of the low-voltage
installation. Examples include measurements on primary
Ⅳ
overcurrent protection devices and electricity Instruments
Motor and Phase Rotation Indicator/English
Measurements
on
battery
powered
7