Wiring the TM-IM/EM, TM-EM/EM terminal submodule
• When laying the cable and connecting the submodule,
observe the regulations in EN 60079-14 plus any
applicable national regulations
• In wiring the submodule, you must strictly separate the
intrinsically safe lines from the non-intrinsically safe. They
must be laid in separate cable ducts.
• Each of the intrinsically safe circuits in the electronic
submodule are to be laid separately and should not be laid
together with the ground wires. When
performing the installation and setup, observe the EN
60079-14 regulations.
• Encoders / HART field devices from Zone 0, Zone 1, Zone
2 as well as Zone 20, Zone 21, Zone 22 and the secured
area may be connected to the terminal submodule. The
terminal assignment of the electronic submodule can be
found in the SIMATIC Distributed I/O ET 200iSP manual.
• The safety data (maximum values) for the sensors / HART
field devices must be adjusted to the electronic
submodule's corresponding maximum values. The
maximum values of the sensors/actuators can be found in
the associated ex certificates. In accordance with EN
60079-14, the following applies:
U
≤ U
; I
≤ I
; P
≤ P
; C
≥ C
+ C
; L
0
i
0
i
0
i
0
i
Line
English
≥ L
+ L
0
i
Line