English
Bosch Power Tec GmbH
When mounting the device in a control cabinet,
make sure there is sufficient air circulation
Comply with the following clearances during
installation:
– 300 mm above
– 300 mm below
– 150 mm to the side
– 150 mm in front of the device
– In the case of outdoor installation: 500 mm
clearance from the ground (protection against
damage caused by rodents)
Installation surface
The installation surface must meet the following
requirements:
Temperature resistant from -45 °C to +150 °C
Made of flame-retardant material. Fitting of metal
plates is not permitted. If mounting on a wooden
wall is unavoidable: Use a 15 mm thick plate (non-
combustible) (e.g. building material class A1)
Fixed
Flat
Large enough
Designed for the weight (Specifications, p. 111)
The mounting background must not transfer
vibrations (e.g. from machines) to the device
Installation altitude
≤ 3000 m
Ambient temperature
During operation, observe the following ambient
temperatures:
T= –10 to +40°C: Optimum ambient temperature:
Device reaches rated power
T= –25 to –10°C and T= +40 to +60°C: Device output
may be reduced (derating). The service life of the
device is reduced.
Transportation and installation | 45
Bosch BPT-S 3 / 3.68 / 4 / 4.6 | Operating manual