6
Function
The safety evaluation unit monitors connected sensors that are equipped with
two make contacts. The safety evaluation unit switches its safety output in ac-
cordance with the operating statuses of the connected sensors.
In the following situations the safety evaluation unit switches off the
safety output:
- All sensors are correctly actuated (safety door(s) closed).
In the following situations the safety evaluation unit switches off the
safety output:
- At least one sensor is not actuated (safety door(s) opened).
- A fault is pending (safety evaluation unit or sensor is defective).
LED displays
LED on
LED
LED state
Terminal /
display
2
Operation
(green)
8
Sensor 1
(green)
12
Sensor 2
(green)
Waiting period
The waiting period is the maximum time permitted on a sensor between the
closing of the first contact maker and the closing of the second contact maker.
Safe condition
- The safety output is opened or with high resistance
7
Technical specifications
See technical specifications beginning on page 9.
8
Installation
Danger of electrocution!
Ensure that the safety evaluation unit is only put into opera-
tion by specially-trained authorized personnel.
Danger
- Installation of the safety evaluation unit is only permitted in a voltage-free state.
- Ensure that the required fuses (see Technical Specifications) are used.
- Snap the safety evaluation unit onto a DIN rail (DIN EN 60715 TH35) in the
switch cabinet. The safety evaluation unit is fixed.
- Connect the safety evaluation unit, see Technical specifications.
- If the sensor input remains free:
Ensure that the make contacts of this sensor input are bypassed.
9
Electrical connection
- The electrical connection is only permitted in a voltage-free state.
- Ensure that the specifications described in the technical specifications are al-
ways complied with.
Upon connection of a sensor, the (+) and (-) sensor supply voltage must be
used by the terminals stated in the technical specifications.
Terminal connections
See technical specifications starting on page 9.
10 Commissioning
Danger of electrocution!
Ensure that the safety evaluation unit is only put into opera-
tion by specially-trained authorized personnel.
Danger
Art.-Nr./Art. No./Réf./N° art/N° art.: 9010029B01M
Meaning
Remedy
No or insuffi-
Check supply voltage.
cient electrical
Check cabling.
off
power supply or
if error persists, replace
serious error
the safety evaluation
unit.
Safety evalua-
on
tion unit is ready
for operation
Serious error
Apply the supply voltage
again.
flashing
if error persists, replace
the safety evaluation
unit.
Sensor not
off
actuated
Sensor correctly
on
actuated
Error on flashing
Actuate sensors again
sensor
(observe waiting period).
flashing
If safety output remains
switched off, replace
safety evaluation unit.
Version/Version/Version/Versione/Versión: 1.1
- Actuate the sensors.
- Apply the operating voltage.
All LEDs light up
The safety evaluation unit performs an internal test.
Upon successful completion of the test the safety evaluation unit switches
through the safety output.
The safety evaluation unit is ready for operation.
NOTE
Upon initial commissioning of a safety evaluation unit, complete validation ac-
cording to the relevant standards must be carried out.
11 Maintenance
The switching behaviour and sequences of every safety circuit must be in-
spected at least once per year.
12 Troubleshooting
Restoring the device to a state of readiness for operation
If the safety output is switched off due to a fault at the sensors and the corre-
sponding LED sensor flashes:
- Set the faulty safety sensor to its non-actuated status and then actuate it again.
The corresponding LED sensor lights up again.
The safety evaluation unit switches through the safety output.
Safety output remains switched off:
- Replace the sensor.
LED U
is flashing
B
- Apply the operating voltage again.
LED U
is still flashing:
B
- Replace the safety evaluation unit.
LED U
is not indicating operational readiness
B
- Check operating voltage.
- Check cabling.
Operating voltage and cabling are OK:
- Replace the safety evaluation unit.
13 Disposal
Dispose of packaging and used parts in accordance with the regulations of the
country in which the device is installed.
Unité d'évaluation de sécurité
463 111 B1 01 / 463 114 B1 01
Traduction de la notice d'utilisation d'origine
1
À propos de cette notice d'utilisation
Valable pour
- 463 111 B1 01
- 463 114 B1 01
La notice d'utilisation doit être mise à disposition de la personne chargée d'ins-
taller l'unité d'évaluation de sécurité.
La notice d'utilisation doit être conservée dans un état lisible et doivent être
accessibles.
Signification des symboles utilisés:
 Attention
En cas de non-respect des instructions, des pannes ou des
dysfonctionnements risquent de se produire.
Le non-respect des instructions peut entraîner des blessures
et/ou des dommages matériels.
2
Utilisation conforme à l'usage prévu
En tant que partie d'une installation globale ou d'une machine, l'unité d'évalua-
tion de sécurité sert à assurer des fonctions de sécurité.
Pour ce faire, les signaux de capteurs de sécurité sont surveillés. Le produit
doit uniquement être utilisé conformément aux descriptions suivantes.
Datum/Date/Date/Data/Fecha: 26.06.2019
FRA
DEU
3/11

Publicidad

loading

Este manual también es adecuado para:

463 114 b1 01