Descargar Imprimir esta página

Waeco AirCon Service Center BMW5500G RPA Instrucciones De Uso página 95

Estación de mantenimiento de aire acondicionado

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

BMW5500G RPA
7.9
Editing default values
The AirConServiceCenter has preset values for the most important ser-
vice tasks. The default values appear automatically when you select the
respective menu.
You can alter the following default values if necessary:
Parameter
Pressure increase test time min.
Vacuum time min.
Leak test min.
PAG oil ml. (additional quantity)
UV tracer ml.
Filling Qt. g.
Print recovery value?
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor key  to select "Service".
4. Press ENTER to confirm.
5. Enter the password "3724".
6. Use the keypad and the cursor keys to enter the information.
7. Press ENTER to confirm.
8. Press STOP to access the standby menu.
EN
Short selection
Free selection
Other selections
ENTER-OK
Initial start-up
Default value
1
20
4
0
7
500
Yes
95

Publicidad

loading