Bench 2 parameters (Bk2)
Abbreviation
Description
SP2
Set-Point
Pb2
Proportional band
Hi2
Maximum speed limit
Lo2
Minimum speed limit
De2
Acceleration time
Sh2
Forced to 100%
Ih2
Hysteresis on Sh1
S02
Forced to 0%
i02
Hysteresis on S01
HP2
Heat pump speed
7.1 Parameters for condensers coupled with inverter
compressors (CR011RA and CR021RA)
When HCR condenser will be connected to a CR011RA or
CR021RA (unit with Inverter Compressor) will be necessary
proceed as following:
1. Digital Filter OFF – DSw>8=OFF (see pag.7)
2. Select Bench Parameters (BK2)
3. Modify below parameter values:
Default parameter edit procedure
Proceed as follows to edit one or more parameters:
1.
Simultaneously press the ENT and ESC keys located under
the display;
2.
Using the or keys, scroll available parameters until the required
one is found;
3.
When the parameter is found, press ENT. "Program" will
switch to "Modify";
4.
Press to increase or to decrease the selected parameter value
(hold down to change faster);
5.
Press ENT to confirm changes;
6.
To edit another parameter, restart from point 2 or
simultaneously press the ENT and ESC keys to save changes
("Update" appears), or press ESC to cancel the operation and
return to the main screen.
N.B.:
If, due to incorrect parameter settings, the regulator has regulation
problems, we recommend you restore default parameters
Liebert
HCR - UM - 265224_EN - 13.10.2022
®
Default Range
U.M.
20.2
0/45
bar
5.4
1/45
bar
100
0/100
%
25
0/100
%
2
2/60
sec
32.4
0/45
bar
1
0.1/15
bar
16.1
0/45
bar
4.1
0.1/15
bar
100
0/100
%
S02 =19.2bar
I02=1.0bar
Default parameter restore procedure
Proceed as follows to restore default parameters:
1.
Press and hold down the SB1 key;
2.
Simultaneously press and hold down the ENT and ESC keys
located under the display;
3.
Release the SB1 key;
4.
Wait until: "Configuration store Default" appears;
5.
Simultaneously release the ENT and ESC keys
LED
COLOR
LABEL
GREEN
PWR
GREEN
RUN
RED
FAIL
GREEN
OUT
GREEN
Signals
Circuit breaker and short circuit protection
A series of fuses (Protistor fuses) are installed on the ESD regulator
to protect the power module.
A circuit breaker (max 20A) with AC trigger curve installed upstream
from the regulator is recommended.
SURGE ARRESTER :
Electrical protection inserted between the regulator power supply
and grounding, that protects the device from transitory power
surges.
WARNING:
Disconnect the faston contact from the PE ground
reference, in the electrical rigidity test.
WARNING:
For
DIFFERENTIAL
components with grounded current dispersion ≥ 60 mA.
ESD has a grounded current dispersion of about 1 mA.
DESCRIPTION
Power on
(light on)
Microprocessor running
(blinking light)
Fault alarm
(see point 5.3.2)
Output command
(light on)
RL1 relay excited
-
(light on)
(see point 3.3.2)
protection
systems,
use