LERBAKKEN 10, 8410 RØNDE DENMARK.
CSA Installation Drawing 533XQC03.
5331D, 5333D and 5335D transmitters are intrinsically safe in Zone 0 Group IIC or Class I,
Division1, Group A,B,C,D when installed according to Installation Drawing.
1. Connections with separate power supply and receiver
Output: Standard 4 – 20 mA loop
Receiving
Instrument
-
+
-
Separate Power
Supply
+
CSA approved
Barrier
+
-
Ambient temperature limits
T4:-40 to + 85 deg. Celcius
T6:-40 to + 60 deg. Celcius
1
6
5
4
SENSOR
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the
Canadian Electrical Code (CEC).
Revision date:
Version Revision
2009-09-22
V1R0
5335QE01
WWW.PRELECTRONICS.COM
Non
Intrinsically safe
hazardous
Barrier Parameters.
Location
max 250V
Uo(Voc)
=< 30V
Io(Isc)
=< 120mA
Po
=< 0,84 W
Co(Ca)>Sum(Ci+Ccable)
Lo(La)>Sum(Li+Lcable)
5331D or
Terminal: 1-2
5333D or
Ui(Vmax) = 30V
5335D
Ii(Imax)
= 120mA
Pi
= 0.84W
Ci
= 1 nF
Li
= 10 uH
Hazardous
5331D or
Terminal: 3,4,5,6
Locations /
5333D
Only passive, or non-energy
2
Sécurité
storing devices such as
Intrinséque
RTD's and Thermocouples
may be connected.
3
5335D
Terminal: 3,4,5,6
Uo(Voc) = 9,6V
Io(Isc)
= 28mA
Po
= 67,2mW
Co(Ca)
= 3,5uF
Lo(La)
= 35mH
5335V112
LERBAKKEN 10, 8410 RØNDE DENMARK.
2. Connection with power supply and barrier built into receiver
Output: Standard 4 – 20 mA loop
Intrinsically safe
Barrier Parameters.
Uo(Voc)
=< 30V
Io(Isc)
=< 120mA
Po(Pmax) =< 0,84 W
Ca>Sum(Ci)+Ccable
La>Sum(Li)+Lcable
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Warning:
Substitution of components may impair intrinsic safety.
The Transmitters must be installed in a suitable enclosure to meet installation codes stipulated in
the Canadian Electrical Code (CEC).
Page:
Revision date:
1/2
2009-09-22
WWW.PRELECTRONICS.COM
Transmitter
Power Supply
built into
CSA approved
Receiving
Instrument
+
-
Terminal: 1-2
5331D or
Ui(Vmax) = 30V
5333D or
Ii(Imax)
= 120mA
5335D
Pi
= 0.84W
Ci
= 1 nF
1
2
Li
= 10 uH
Terminal: 3,4,5,6
5331D or
6
3
Only passive, or non-energy
5333D
storing devices such as
5
4
RTD's and Thermocouples
may be connected.
SENSOR
Terminal: 3,4,5,6
5335D
Uo(Voc) = 9,6V
Io(Isc)
= 28mA
Po
= 67,2mW
Co(Ca)
= 3,5uF
Lo(La)
= 35mH
Version Revision
V1R0
5335V112
5335QE01
Non-
hazardous
location
max 250 V
Hazardous
Locations /
Sécurité
Intrinséque
Page:
2/2