TROUBLE SHOOTING CHART
PROBLEM
Unit will not start
Insufficient Cooling
Water in air stream
High indoor humidity
Odor in home
Rapid mineral buildup on
media pads
PROBABLE CAUSE
a. No Power
b. Tripped Circuit Breaker
c. Blown home fuse
d. Electrical fault
a. Inadequate water distribution (pads not
saturated)
b. Pads dirty or covered with mineral
deposits
a. Water system has leaks or loose
connections
b. Water is not being absorbed by media
pads, and entering straight into airflow
a. Insufficient air flow
b. Unsatisfactory exhaust
a. Occurs initially when pads are first
saturated
b. Bacterial growth in reservoir
c. Air intake is picking up ambient odor
from surroundings
a. Hard water
SOLUTION
a. Verify unit plugged in; and outlet is functional
b. Reset Circuit Breaker
c. Replace home fuse
d. Call Champion Help line: 1.800.643.8341
a. Check water distribution tray and hose for
blockages.
- Verify pump operating correctly
- Check water supply for correct flow
b. Wash dirt & deposits off pads or replace pads
a. Check all water connections, tubing, distribu-
tion tray for loose fittings, leakage or tears.
b. Check condition of pads. Clean or replace as
necessary.
a. Increase fan speed
b. Open doors or windows more
a. Normal. Will dissipate shortly.
b. Clean unit regularly
c. Remove source of odor or move cooler to
another window
a. Install purge pump to reduce build-up.
b. Increase maintenance cycle and wash off
scale more often. Check orifices are clear of
mineral buildup.